Dip-switch setting
1. address setting
Total of eight bits dip-switch,fore four bits are for module chiller address
setting,and moudule chiller network can just have one master unit,and every module
chiller's address cannot be same.
The first~fourth bits are for module chiller selection:
DIP1 DIP2
DIP3 DIP4
ON
ON
ON
ON
ON
ON
ON
ON
OFF
ON
ON
OFF
ON
OFF
ON
ON
OFF
ON
ON
OFF
OFF
ON
OFF
OFF
OFF
ON
ON
OFF
ON
ON
OFF
ON
OFF
OFF
ON
OFF
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
Notes:module chiller can connect 16 pieces of units at the most to compose network
Slave address setting had better set as sequence continuously(1、2、3 ......by
turns adding continuously)
2. Type setting
2.1 the fifth bit setting is for unit type selection
The fifth bit sets "ON",cooling only
The fifth bit sets"OFF",heat pump.
2.2 the sixth bit is for 30 or 70 unit type selection
The sixth bit sets "ON",33C
The sixth bit sets "OFF",65C
NOTES: The last two bits are not difined,and usual set "OFF" when out of factory.
address
ON
master unit 0
OFF
slave unit 1
ON
slave unit 2
OFF
slave unit 3
ON
slave unit 4
OFF
slave unit 5
ON
slave unit 6
OFF
slave unit 7
ON
slave unit 8
OFF
slave unit 9
ON
slave unit 10
OFF
slave unit 11
ON
slave unit 12
OFF
slave unit 13
ON
slave unit 14
OFF
slave unit 15
HAIER CHILLER