Wiring
The safety related terminals are described in Table 3 and Table 4.
Terminal
Terminal name
symbol
Safety stop input
S1
(Channel 1)
Safety stop input
S2
(Channel 2)
PC
24 VDC power supply
SO
Inverter running status
Safety monitor output
SOC
terminal common

Specifications for conforming to safety standards.

ON: The transistor is conducted. OFF: The transistor is not conducted.
Table 3 Safety related terminals
Terminal function description
For input of safety stop channel 1
Between S1 and PC
OFF: In safety stop mode
ON: Other than the safety stop mode
For input of safety stop channel 2
Between S2 and PC
OFF: In safety stop mode
ON: Other than the safety stop mode
-
Used for internal safety circuit failure detection and
alarm (open collector output).
Between SO and SOC
OFF: Internal safety circuit failure or alarm detected
ON: No internal safety circuit failure
Note: Terminal SO cannot be used for safety signals in a
safety system. Use terminal SO to output a fault
and to prevent restarting of the inverter.
Common terminal for terminal SO

Input resistance: 4.7 kΩ
Input current: 4 to 6 mADC
(In case of 24 VDC input)
Output voltage: 22 to 26.5 V
Output current: 100 mA max.
Load: 24 VDC / 0.1 A max.
Voltage drop: 3.4 V max.
(In case of 'ON' state)
INSTALLATION AND WIRING
Rating

5