Compliance with the EU Machinery Directive – Functional Safety
To achieve functional safety, any work on the product such as wiring and inspections must be performed according to the
Instruction Manual by technicians who took a safety standard training.
WARNING
 Any misuse of safety function could lead to personal injury or death, property damage, or economic
loss. To ensure that the system complies fully with requirement of safety, make a system-level risk
assessment. Mitsubishi Electric cannot assume responsibility for any system to comply with safety
directive.
 To avoid an electric shock hazard, verify that the voltage on the bus capacitors has discharged
before performing any work on the inverter. Measure the DC bus voltage between the terminals P/+
and N/- or at test points (refer to your inverter's Instruction Manual for locations and discharging
time). The voltage must be zero.
 The safety stop function do not isolate electrically between the inverter and the motor. To avoid an
electric shock hazard, verify that the voltage on the bus capacitors has discharged before wiring or
inspection of the motor. Measure the DC bus voltage between the terminals P/+ and N/- or at test
points (refer to your inverter's Instruction Manual for locations and discharging time). The voltage
must be zero.
CAUTION
 The information of this manual is merely a guide for proper installation.
 Mitsubishi Electric cannot assume responsibility for the compliance or the noncompliance to any
code, national, local, or otherwise for the proper installation of this equipment.
 A hazard of personal injury and/or equipment damage exists if codes are ignored during installation.