Operating range

Content
Chilled Leaving Water Temperature
Cooling Entering water Temperature
Water flow volume
Max inlet/outlet water Temp. difference
Voltage tolerance
Phase tolerance
Power supply frequency
Evaporator max working pressure on water side
Compressor max. start count
Environment quality
Drainage system
Normal operation ambient temperature
Storage and transport temperature
Applicable altitude range:
LSBLG/MCF evaporator
Entering temperature at start-up
Leaving temperature during operation
Entering/leaving temperature difference at full load
LSBLG/MCF condenser
Entering temperature at start-up
Leaving temperature during operation
Entering/leaving temperature difference at full load
Note:
(1)
For low-temperature applications, where the leaving water temperature is below 4° C, the anti-freezing protection switch
will stop the unit stop from running.
(2)
If the temperature leaving the condenser is below 19° C,the unit will stop and give a warning
(3)
Ambient temperatures: During storage and transport of the LSBLG/MCF units. Including by container) the minimum
and maximum permissible temperatures are -20° C ~ 46° C(R134a);
Changes water temperature curve in the operation
Flooded type water cooled screw chiller (MIC)
Running range
5℃~15℃
25℃~35℃
Flow volume rating± 20%
8℃
Rating Voltage ± 10%
± 2%
Rating frequency± 2%
1.0MPa
4 times/h 8 times/day
Highly corrosive environments and high
humidity should be avoided.
The height of water drainage should not be
higher than the base of the unit on the spot
-10℃~45℃
-25℃~50℃
Less than 1000m
Minimum
8° C
5° C
3.8° C
Minimum
19° C
22° C
3.8° C
25
Maximum
25° C
15° C
8° C
Maximum
35° C
42° C
8° C