7.

Water flow

Balance the chilled water flow through the evaporator and the condenser water flow through the
condenser. The flow rates must fall between the minimum and maximum values shown in the table
below. Flow rates below the minimum values shown will result in laminar flow which will reduce
efficiency, cause erratic operation of the electronic expansion valve and cause low temperature cutouts.
On the other hand, flow rates exceeding the maximum values shown can cause erosion on the heat
exchanges water connections and tubes, even piping breaking.
Variable chilled water flow through the heat exchanges while the compressor(s) are operating is not
recommended. The chiller control set points are based upon a constant flow and variable temperature.
Model
LSBLG340/MCF
LSBLG440/MCF
LSBLG540/MCF
LSBLG720/MCF
LSBLG805/MCF
LSBLG890/MCF
LSBLG1055/MCF
LSBLG1200/MCF
LSBLG1300/MCF
LSBLG1410/MCF
LSBLG1620/MCF
LSBLG1780/MCF
Pressure drop
Evaporator
Water pressure drop curve(evaporator)
60
50
40
30
20
10
0
0.0
50.0
Evaporator water flow rate
Rated
Minimum
58
29
76
38
93
46
124
62
138
69
153
77
182
91
206
103
224
112
243
122
279
142
306
153
100.0
150.0
3
Water flow(m
/h)
3
m
/h
Condenser water flow rate
Maximum
Rated
64
73
83
95
102
116
138
155
152
173
168
191
200
227
227
258
246
280
267
303
312
348
337
383
200.0
250.0
22
MCAC-CTSM-2018-1
3
m
/h
Minimum
Maximum
37
80
47
104
58
128
74
173
87
190
96
210
113
250
129
284
140
308
152
333
177
390
191
421
LSBLG340/MCF
LSBLG440/MCF
LSBLG540/MCF
LSBLG720/MCF
LSBLG805/MCF
LSBLG890/MCF
LSBLG1055/MCF