Installation Procedure
◆ AJ030TXS4CH / AJ036TXJ4CH / AJ036TXS4CH
1 Piping outside diameter.
Indoor unit
**07/09/12/009/
012**, AR15**
AJ030TXS4CH /
**18/018**,
AJ015**
**24**
2 Piping length and the height.
1 Room
max
length
Dimension
82.0 ft
Composition A,B,C,D
CAUTION
• 10 ft as minimum pipe length: It will reduce noise and
vibration.
• The appearance of the unit may be different from the
diagram depending on the model.
18
English
DB68-08940A-00_IM_FJM Outdoor_AA_EN.indd 18
Power
Outside
Out unit
supply Ø,
diameter
V, Hz
Liquid Gas
1,208-
1/4"
AJ036TXJ4CH
230,60
A
B
C
D
Main power switch
Max height
Max height
4 Room
between
between
total max
indoor unit &
indoor
length
units
outdoor unit
229.7 ft
49.2 ft
24.6 ft
A+B+C+D
(H)
Make at least one round:
It will reduce noise and vibration
◆ AJ048TXJ5CH
1 Piping outside diameter
Indoor unit
3/8"
**07/09/12/009/
012**, AR15**
1/2"
**18/018**,
5/8"
AJ015**
**24**
(h) (H)
2 Piping length and the height.
1 Room
max
length
(h)
Dimension
82.0 ft
Composition A,B,C,D,E A+B+C+D+E
CAUTION
• 10 ft as minimum pipe length: It will reduce noise and
vibration.
• The appearance of the unit may be different from the
diagram depending on the model.
Outside
Power
diameter
Out unit
supply Ø,
V, Hz
Liquid Gas
AJ036TXS5CH /
1,220-240,
1/4"
AJ048TXJ5CH
50
A
B
C
D
E
Main power switch
Max height
5 Room
between
height
total max
indoor unit
between
length
& outdoor
indoor
unit
229.7 ft
49.2 ft
24.6 ft
(H)
Make at least one round:
It will reduce noise and vibration
2020-01-23 오후 12:38:04
3/8"
1/2"
5/8"
(h) (H)
Max
units
(h)