Nibe F1155PC Installation Manual page 41

Ground source heat pump
Table of Contents

Advertisement

Caution
If no alarm action is selected, it can result in
higher energy consumption in the event of an
alarm.
MENU 5.1.5 - FAN SP. EXHAUST AIR
(ACCESSORY IS REQUIRED)
normal and speed 1-4
Setting range: 0 – 100 %
Set the speed for the five different selectable speeds
for the fan here.
Caution
An incorrectly set ventilation flow can damage
the house and may also increase energy con-
sumption.
MENU 5.1.7 - BR PMP AL SET.
min. brine out
Setting range: -12 – 15 °C
Default value: -8 °C
min. brine out
Set the temperature at which the heat pump is to activ-
ate the alarm for low temperature in outgoing brine.
If "automatic reset" is selected, the alarm resets when
the temperature has increased by 1 °C below the set
value.
The compressor winds down when the brine temperat-
ure reaches the set minimum value for brine temperat-
ure. Compressor control attempts to maintain the brine
at a temperature 2 ° greater than the set value for brine
out.
MENU 5.1.8 - OPERATING MODE BRINE
PUMP
op. mode
Setting range: intermittent, continuous, 10 days
continuous
Default value: intermittent
Set the operating mode of the brine pump here.
intermittent: The brine pump starts approx. 20 seconds
before and stops approx. 20 seconds after the com-
pressor.
continuous: Continuous operation.
10 days continuous: Continuous operation for 10 days.
The pump then shifts to intermittent operation.
NIBE F1155PC
TIP
You can use "10 days continuous" at start-up
to obtain continuous circulation during a start-
up time in order to make it easier to bleed the
system.
MENU 5.1.9 - BRINE PUMP SPEED
op. mode
Setting range: auto / manual / fixed delta
Default value: auto
delta T
Setting range: 2 - 10 °C
Factory setting: 4 °C
speed in wait mode
Setting range: 1 - 100 %
Factory setting: 70 %
Speed extern. contr. (AUX)
Setting range: 1 - 100 %
Factory setting: 100 %
manual
Setting range: 1 - 100 %
Factory setting: 100 %
speed passive cooling
Setting range: 1 - 100 %
Factory setting: 75 %
Delta in the case of passive cooling
Setting range: 1 - 15 °C
Factory setting: 4 °C
speed in wait mode cooling
Setting range: 1 - 100 %
Factory setting: 30 %
temperature difference, active cooling
Setting range: 2 - 10 °C
Factory setting: 5 °C
Set the speed of the brine pump here. Select "auto" if
the speed of the brine pump is to be regulated automat-
ically (factory setting) for optimal operation.
Chapter 8 | Control - Menus
41