Mpi Connection - Siemens SIMATIC WinAC Slot 412 Manual

Windows automation center
Table of Contents

Advertisement

Establishing a connection

MPI connection

1. Select the "Router" project.
2. Double-click MPI(1) to open it.
3. Double-click the MPI/DP node of the Box PC 620 to select it.
4. Select "MPI(1)" from the subnet list.
5. Open the properties dialog box, change the network name from "MPI(1)" to
"MPI-Net".
6. Set address "2".
7. Double-click the CPU 416-1 to select it.
8. Select "MPI-Net" from the subnet list.
9. Open the properties dialog, and select MPI-Net.
10.Set address "10".
11. Click "OK" to apply the dialogue.
12.Close with "Save and Compile".
Figure 3-6
MPI Connection
Windows Automation Center WinAC Slot 412/WinAC Slot 416 Version 3.1
A5E00065531-03
Getting Started
3-7