SC-2062 Board

Power Requirement (from Host Board or External Power Supply)

Field connections
Power consumption (at +5 VDC)
All relays energized (typical)
No relays energized (typical)
Maximum
Note:
The power specifications pertain to the power supply of the host computer when using
internal power or to the external supply connected at screw terminal J2 when using
external power.

Physical

Board dimensions (including standoffs)
I/O connectors

Operating Environment

Temperature
Relative humidity

Storage Environment

Temperature
Relative humidity

Mounting and Connection to Data Acquisition Boards

The SC-2062 has metal standoffs so the board can sit on a workbench near the host computer.
You can use an optional rack-mount chassis, which can be fitted with a flat acrylic plastic cover.
The SC-2062 grounds to its metal standoffs, and thus to the rack, when it is mounted in the
chassis.
Warning:
The SC-2062 must be completely enclosed if any onboard voltages or any voltages
connected to the relays can exceed 30 V.
SC-206X Series User Manual
3 screw terminals per channel
490 mA ±5%
10 mA ±5%
630 mA
5.2 by 4.9 by 1.8 in.
One 26-pin male ribbon-cable connector
26 screw terminals
0° to 70° C
5% to 90% noncondensing
-55° to 130° C
5% to 90% noncondensing
4-4