Problem Reports
•
•
Table
Table 6-1. IMASI23 Error Types
Error
Error Description
Type
14
Calibration (0EH) problem
report (from FC 216)
Calibration (0EH) problem
report (from FC 215)
Calibration (0EH) problem
report (from FC 216)
Calibration (0EH) problem
report (from FC 215)
7
Configuration mismatch
problem report (from FC 216)
3
Channel failure/out of range
(03H) problem report (from
FC 216)
Channel failure/out of range
(03H) problem report (from
FC 215)
Channel failure/out of range
(03H) problem report (from
FC 216)
Channel failure/out of range
(03H) problem report (from
FC 216)
Channel failure/out of range
(03H) problem report (from
FC 215)
6 - 2
If the detailed module status read from the ASI module by
the controller indicates any error conditions.
If the channel status for any configured channel indicates
an error.
6-1
contains the error types generated for each error.
Module Problem Report Type 12
Analog Input Module
Error
Channel 1-16 disabled Remove IMASI23 and reinsert. If
Cold junction disabled
Channel 1-16 not
calibrated
Cold junction not
calibrated
Channel not configured Verify that Specs S3 through S9 of
Channel 1-16 out of
range error
Cold junction out of
range error
External cold junction
reference error
Channel 1-16 A/D
conversion error
Cold junction A/D con-
version error
Corrective Actions
error recurs, replace the IMASI23.
the indicated FC 216 are correct.
Possible open input or signal is
out of range. Verify field wiring,
connections, sensor and module
seating.
Verify quality of block defined for
Spec S3.
Remove IMASI23 and reinsert. If
error recurs, replace the IMASI23.
WBPEEUI240774A0