Fan Speed (U4); Dhw/Return Temperature Setting (U5); Anti-Legionella Function (U6) - Geco GH11RA User Instructions

Instruction of controller operation for controlling central heating boilers with feeding screw
Table of Contents

Advertisement

USER INSTRUCTIONS GH11RA

6.5. Fan Speed (U4)

This setting determines the fan rotation speed, and thus the amount of air delivered. It allows to adjust
the fan speed according to the type and quality of the fuel used.
This setting can be set within the range of 1÷10, where "1" denotes minimum speed, and "10" maximum
speed.
You can modify this setting in a similar way to the described in sections 6 and 6.2.

6.6. DHW/Return Temperature Setting (U5)

This setting is available to the user only if the DHW heating option or return temperature stabilisation
are used, and the user configured the pump with the F00 service parameter by setting it to the values "01",
"02", "03", "04" (⇒ section 8.2 page 8). You can modify this setting in a similar way to the described in
sections 6 and 6.2. Settings are within the range of 35°C to 65°C.

6.7. Anti-Legionella Function (U6)

To activate the ANTI-LEGIONELLA function, set the U6 setting to 1.
When the function is active, a blinking letter "L" is visible on the left part of the display, before the
displayed temperature value.
You can turn off the function by modifying the U6 setting to 0, or by pressing
function is also cancelled after a power down.
The ANTI-LEGIONELLA function has higher priority over other functions, therefore it is performed
by the Controller in the first order (superior function).
When the function is activated, the temperature of water in the boiler is increased to 70°C and maintained
for a period of 10 minutes.
TURNING ON OF THE ANTY-LEGIONELLA FUNCTION CAUSES RISE OF
Wydanie I
THE TEMPERATURE OF HUW WATER UP TO 70
EXTRA CAUSION WHEN USING HUW.
MAY RESULT IN BURNING !!!
STRONA 13
. The anti-legionella
0
C.
STYCZEŃ 2010