Redring POWERSTREAM ASCARI PSA 12 Installation Manual page 33

Table of Contents

Advertisement

Press
and
Condition
Parameter #
Manufacturer
If
= 1
or 2
if
= 1
or 2
if
= 1
if
= 1
if
= 1
if
= 1
if
= 1
If
= 4
or 6
if
= 0
if
= 0
if
= 0
if
= 0
if
= 0
if
= 0
Manufacturer
: See § 7 to set the heating diagram according to 4 paremeters (TCMA, TCMI, TEMA and TEMI)
(1)
: Prohibited when using a scheduled external command
(2)
: Depending on water flow rate and volume inside the heating circuit, the boiler might start at very short
(3)
intervals with wear and tear resulting. To reduce the number of cycles, increase delay.
N
: To reset autoadaptability, zero parameter #
ote
PARAMETERS LISTING
during 3 sec to access parameters menu.
Description
Output level number
Maximum requested boiler's temperature
(1)
(TCMA)
Minimum requested boiler's temperature
(1)
(TCMI)
Ambience thermostat connected (no = 0 ;
thermostat = 1 ; sensor = 2)
Heating circuit pump monitored by ambience
thermostat (no = O ; yes = 1)
Autoadaptability or automatic correction of the
heating diagram or the requested temperature
(no = O ; yes = 1)
Outside sensor (no = O ; yes = 1)
(1)
Maximum outside temperature (TEMA)
(1)
Minimum outside temperature (TEMI)
Automatic summer switch
(no = O ; yes = 1)
Delay between 2 steps activation and
deactivation
Domestic Hot Water production
(no = 0 ; yes = 1)
Domestic Hot Water probe
(no = 0 ; yes = 1)
Legionnaires disease free mode
(no = 0 ; yes = 1)
Power levels peering
Connection of 6 power steps
(no = 0 ; yes = 1)
Connection of power step 1
(no = 0 ; yes = 1)
Connection of power step 2
(no = 0 ; yes = 1)
Connection of power step 3
(no = 0 ; yes = 1)
Connection of power step 4
(no = 0 ; yes = 1)
Connection of power step 5
(no = 0 ; yes = 1)
Connection of power step 6
(no = 0 ; yes = 1)
Timer input allocation (no = 0 ; Lowering of
Eco boiler requested temperature = 1 ;
Lowering of frost protection boiler requested
temperature = 2 DHW autorisation = 3)
Water pressure sensor
POWERSTREAM Ascari -p. 33 -
, then set value to 1.
Available
ex-work settings
settings
Depending to the boiler
2 ; 3 ; 4 ; 5 or 6
21 to 80°C
21 to TCMA °C
0 ; 1 or 2
0 or 1
(2)
0 or 1
0 or 1
0 mandatory
11 to 25°C
-30 to +10°C
0 or 1
(3)
1 to 6 min
0 or 1
(4)
0 mandatory
0 or 1
(5)
0 or 1
0 or 1
0 mandatory
0 or 1
0 or 1
0 or 1
0 or 1
0 or 1
0 or 1
0 or 1
0 ; 1 ; 2 or 3
0 mandatory
0 or 1
Output
75°C
50°C
1
1
1
20°C
-5°C
0
2 min.
0
0
1
1
1
1
1
1
1
1