2.4.2 - Electrical Compartment

With the cover removed access to the electrical connections is achieved by undoing the screw of the electric box.
Once opened access is gained to the electrical connectors, for easy installation.

2.4.3 - Selecting Thermal cut-out

The thermal cut-outs are situated at the top of the boiler and may be selected during the installation by re-routing
the electrical connections. The boiler is factory set with the 100
systems. If the Boiler is to be used with underfloor heating remove the connectors from the 100
connect to the 60
C sensor ensuring there is a good connection.
o
Where both underfloor and hot water cylinder are used, it is necessary to use the 100°C temperature cut-out in
the boiler and include a separate 60°C thermal cut-out for the underfloor heating circuit.
Connector
60°C
Thermal cut-out selection
(100°C for radiators, 60°C for underfloor)
POWERSTREAM Ascari -p. 13 -
C cut-out selected for use with radiator heating
o
100°C
C sensor and
o