Download Print this page

Specifications - Tripp Lite SM3000RMNAFTA Specification Sheet

Smart pro line interactive 2u rack/tower extended run ups - nafta assembled version of smart3000rm2u

Advertisement

control
Built in Emergency Power Off (EPO) interface with cable
Sine wave output in AC and battery modes
Expandable runtime with optional battery packs BP48V24-2U (limit 1) and BP48V60RT-3U (multi-pack compatible)
Some external battery configurations require the use of Tripp Lite's
Half load runtime of 11 minutes (1125 watts)
Full load runtime of 4 minutes (2250 watts)
Includes 9 output receptacles arranged in 3 load banks (4 NEMA 5-15R / 4 NEMA 5-15/20R / 1 NEMA L5-30R)
Ships with NEMA L5-30P input plug, user installable NEMA 5-20P replacement plug included
Integrated 3 bank switched PDU enables remote outlet management for load shedding or remote reboot of individual devices
3 stage metered LEDs offer current monitoring and battery charge level
Mains power and voltage regulation LEDs offer at-a-glance power status information
Front panel switches support self-test and alarm cancel functions
Included UPSRMRII adjustable mounting rails support installation in 19 inch racks with a front-to-rear depth of 23.5 and 36.5 inches (add a
2nd UPSRMRII accessory to extend the reach to 35.25 to 49.5 inches)
UPS ships fully assembled in full compliance with DOT regulations, no time consuming connection of internal batteries by user required
Supports 2 post rackmount and wallmount installation with optional 2POSTRMKITWM accessory
Supports upright tower placement with optional 2-9USTAND accessory
UL (USA), cUL (Canada), NOM (Mexico), FCC Class A (Emissions) listed
$250,000 Ultimate Lifetime Insurance

Specifications

OUTPUT
Output Volt Amp
Capacity (VA)
Output kVA capacity
(kVA)
Output Watt Capacity
(watts)
Output kW capacity
Output power factor
Nominal Output
Voltage(s) Supported
Frequency compatibility
Output voltage
regulation (line mode)
Output voltage
regulation (Battery mode)
Built-in UPS output
receptacles
Built-in controllable
switched load banks
Output circuit breaker
Basic PDU options
Metered PDU options
Switched PDU options
Output AC waveform (AC
mode)
3000
3
2250
2.2
0.8
120V
60 Hz
-18%, +8%
+/- 5%
4 5-15R outlet(s); 4 5-15/20R outlet(s); 1 L5-30R outlet(s)
Three switchable single-outlet 5-15R load banks
20A (x2) - each breaker protects 4 5-15/20R outlets, L5-30R is unbreakered
PDU2430
(1U / 24 5-15R outlets)
PDUMV30
(0U / 24 5-15/20R outlets)
PDUMH30NET
(2U / 16 5-15/20R outlets);
Sine wave
External Battery Configuration Software
PDUMV30NET
(0U / 24 5-15/20R outlets)
(see manual)

Advertisement

loading