Carrier 30HWA Series Installation Instructions page 2

50/60 hz accessory sound enclosure for hwb018-040

Advertisement

Fig. 1 — Installing Insulated Basepan Assemblies in Unit Upper Section
Fig. 2 — Installing Insulated Basepan Assemblies in Unit Lower Section
Step 2 — Check Unit Disconnect Switch Amps
If unit is equipped with factory-installed 100- or 200-
amp non-fused disconnect switch, you must remove the dis-
connect switch before installing the accessory sound
enclosure.
To remove the switch, first disconnect the electrical con-
duit and wiring to the disconnect switch, then remove the 2
upper and 2 lower screws that support the switch. The dis-
connect is to be replaced after sound enclosure kit installa-
tion is completed; save removed screws. It is not necessary
to remove 30- and 60-amp non-fused disconnects (if equipped).
Step 3 — Modify 2 Insulated Basepan Assem-
blies For Upper Section —
sulated basepan assemblies (Item 1). See Fig. 3. These cut-
away areas permit the insulated basepan assembly to fit around
the control box conduit on one side, and around the suction
and discharge tubes on the other side. The remaining 2 in-
sulated basepan assemblies for the unit lower section do not
require any modification.
Cut away part of 2 in-
SUCTION LINE
DISCHARGE LINE
UNIT UPPER BASEPAN
WITH PRE-DRILLED
SCREW HOLES
CUT-AWAY
INSULATION
(SLOT 1)
1
2
3
1
2
3
MODIFIED UPPER
SECTION INSULATED
CUT-AWAY
BASEPANS (2)
INSULATION
(SLOTS 2 AND 3)
UNIT LOWER BASEPAN
WITH PRE-DRILLED
SCREW HOLES
UNMODIFIED LOWER
SECTION INSULATED
BASEPANS (2)
Fig. 3 — Modifying Insulated Basepan Assemblies
for Upper Section
2
PRE-DRILLED
SCREW HOLES
UPPER SUPPORT
ANGLE (ONE EA SIDE)
PRE-DRILLED
SCREW HOLES
LOWER SUPPORT
ANGLE (ONE EA SIDE)