Fujitsu AB F18LAT Series Service Instruction page 52

Split type, room air, conditioner, floor ceiling type, duct type, cassette type models indoor unit outdoor unit inverter
Hide thumbs Also See for AB F18LAT Series:
Table of Contents

Advertisement

Trouble shooting 18
OUTDOOR UNIT Error Method:
INDOOR UNIT
Outdoor unit computer
communication error
Detective Actuators:
Outdoor Unit Main PCB Circuit
Forecast of Cause :
1. Main PCB failure
Check Point 1 : Replace Main PCB
Change Main PCB.
Trouble shooting 19
INDOOR UNIT Error Method:
INDOOR UNIT
Indoor manual auto switch error
Detective Actuators:
Indoor Unit Controller PCB Circuit
Forced auto switch
Forecast of Cause :
1. Forced auto switch failure
Check Point 1 : Check the Forced auto switch
Check if Forced auto switch is kept pressed.
Check ON/OFF switching operation by using a meter.
>>If Forced auto switch is detective, replace it.
OK
OK
Check Point 2 : Replace Controller PCB
If Check Point 1 do not improve the symptom, change Controller PCB.
Indicate or Display:
Outdoor Unit : No indication
ERROR CODE : E : 1c
Detective details:
When it cannot receive an effective signal for 10sec between
the Main CPU and Sub CPU in outdoor unit.
Indicate or Display:
Outdoor Unit : No indication
ERROR CODE : E : 20
Detective details:
When the Forced auto switch becomes ON for 30 consecutive seconds.
2.Controller PCB failure
02-21