Fujitsu AB F18LAT Series Service Instruction page 68

Split type, room air, conditioner, floor ceiling type, duct type, cassette type models indoor unit outdoor unit inverter
Hide thumbs Also See for AB F18LAT Series:
Table of Contents

Advertisement

SERVICE PARTS INFORMATION 2
Inverter Compressor
Check Point 1 : Check Connection
Check terminal connection of Compressor
(loose or incorrect wiring)
Terminal cover opened
C(T)
(BLACK)
(BLACK)
Check Point 2 : Check Winding Resistance
Check winding resistance of each terminal
If the resistance value is 0
R
C(T)
Check Point 3 : Replace Main PCB
If the symptom does not change with above Check 1, 2, replace Main PCB.
R
(RED)
(RED)
S
(WHITE)
(WHITE)
or infinite, replace Compressor.
Resistance Value :
S
Check connection of Main PCB
(Loose or incorrect wiring)
MAIN PCB
WHITE
0.73
(For AOY*18LALL)
0.97
(For AOY*24LALL)
at 20°C
02-37
W8
W7
W9
RED
Compressor
BLACK