Troubleshooting
The UPS's control panel lights will turn on in the sequences below to signal that the UPS is having
operational difficulties.
Lights (On/Flashing) and Condition
On: REPLACE BATT
Condition: Replace Battery
On: BATT LOW, ON BATT
Condition: Battery Low
On: BYPASS, LINE, LOAD, OVERLOAD
Condition: On Bypass due to Overload
Flashing: OVERLOAD
Condition: Short Circuit
On: FAULT
Condition: Wiring Fault
On: FAULT, 100%
Condition: Battery Voltage too High
On: FAULT, BYPASS, LINE, 50%
Condition: On Bypass due to
High Output Voltage
On: FAULT, BYPASS, LINE
Flashing: 50%
Condition: On Bypass due to
Low Output Voltage
On: FAULT, BYPASS, LINE, 25%
Condition: On Bypass due to High
Bus Voltage
On: FAULT, BYPASS, LINE
Flashing: 25%
Condition: On Bypass due to Low
Bus Voltage
On: BYPASS, LINE
Flashing: FAULT
Condition: On Bypass due to High
Internal Temperature
Flashing: LINE
Condition: Input Abnormal
On: FAULT, 50%
Flashing: LINE
Condition: No Output due to High
Output Voltage and Abnormal Input
On: FAULT
Flashing: LINE, 50%
Condition: No Output due to Low
Output Voltage and Abnormal Input
Solution
Let the UPS system charge for at least 12 hours
and perform a self test using the "ON/Test
Switch" as described on page 6. If the light
continues to stay on, contact Tripp Lite for service.
Prepare for imminent UPS shutdown.
Reduce the load the UPS supports.
Remove the cause of the short circuit
from the UPS output.
Check the utility line for wiring problems such as
reversed line and neutral or a missing ground.
Restart the UPS. If the problem persists,
contact Tripp Lite for repairs.
Restart the UPS. If the problem persists,
contact Tripp Lite for repairs.
Restart the UPS. If the problem persists,
contact Tripp Lite for repairs.
Restart the UPS. If the problem persists,
contact Tripp Lite for repairs.
Restart the UPS. If the problem persists,
contact Tripp Lite for repairs.
Check the UPS to be sure that there is
adequate space for air to circulate near
the vents and that the fan is working
properly. Restart the UPS.
This indicates that utility power is too high or low
for the UPS to operate in BYPASS mode, so if an
inverter failure occurs, the UPS will deliver no output.
Restart the UPS. If the problem persists,
contact Tripp Lite for repairs.
Restart the UPS. If the problem persists,
contact Tripp Lite for repairs.