Troubleshooting Guide / Error Codes - sol-ark 12K Install Manual & Owner’s Manual

Hybrid inverter
Hide thumbs Also See for 12K:
Table of Contents

Advertisement

LCD is not powering on
o Check all connections
At least one of the following power sources is required: PV/Grid/Battery
o Try pressing the power button. Or touchscreen or navigation button.
Panels are connected but DC Light is not on
o PV voltage must be 150V-500V
o It's night
Panels are not producing
o Check all solar panel connections are wired properly
o Turn on PV disconnect
o Check that the PV input voltage is not greater than 500V
o If system says PV=0V, check PV polarity
Panels are not producing much power
o PV Wire Strip Length: 5/8". Your batteries maybe charged, you can test Grid Sell to verify.
System not keeping batteries charged
o Check the charge setting in the Charge Menu
Auto Gen-Start not working
o Check to make sure your generator is compatible with Auto Start
o Make sure that the Auto Gen Start wire is connected properly to the Sol-Ark 12K and the generator
Normal LED isn't on
o Sol-Ark 12K is not working properly (Call us)
Alarm Light is on
o Check the system alarms menu to see which alarm has been triggered
Grid HM value is negative when it should be positive (only applies in limited home mode)
o Limiter Sensors are installed backwards or L1/L2 sensors are swapped or L1/L2 sensors mis-wired
AC Overload Fault or Bus Unbalance Fault
o Check Transfer Switch/Subpanel wiring
o Check for large loads that pull more than the inverter is rated for (EX: AC units over 4 tons)
System connects to grid and quickly disconnects
o With a DMM, verify your Neutral wire is connected (should be 0Vac referenced to GND)
o Check your Freq is set to 60Hz and the 12K see's 120V on L1 & L2 to N.
o If overloading: verify 120/240V grid input and load output wires are not swapped.
o If 120/208V, the L1 and L2 are phase specific. So, you may have to swap Grid L1 L2 for 208V applications.
DC Overload Fault
o Check PV voltage
o Make sure you have not wired more than 2 solar stings in parallel
System is beeping
o Check the system alarms menu to see which alarm has been triggered. Most alarms will self-reset.
o There is no battery connected. If not using a battery, select no battery in the setup Batt menu.
To fully reset system, turn off center button, remove AC Grid and PV Power for 30s (screen is
dead), then power up.
Battery cable is sparking when connected
o Put the built-in battery disconnect in the off position before connecting or disconnecting batteries.
Battery symbol on home screen is red
o Battery is under voltage or over voltage
Battery symbol on home screen is yellow
Troubleshooting Guide
February 3, 2020
40