External Wiring

WARNING: All external ports should be equipped with switches.
CAUTION: All cables shall be connected in sequence as listed in this manual.
NOTE: The actual connection depends on your application case. Not all the ports
are necessary to be connected.
Refer to the table below for minimum copper wire sizing and ratings.
(1)
AC/Ground
PV/Battery
12Vdc/AFCI
Communication
Ethernet
Refer to the table below for minimum external switch sizing and ratings
(2)
Connect Universal PCS to ground.
(3)
CAUTION: As the inverter is transformer-free, neither positive nor negative
polarities of PV arrays shall be ground connected; otherwise, it may present
a risk of inverter failure. In a photovoltaic energy system, all metal
components that are non-current-carrying, e.g. brackets, combiner boxes,
distribution boxes, inverter boxes, shall be grounded.
Voltage
Rating
600V
600V
30V
30V
Voltage
Rating
AC
600V
PV
600V
Temp.
Gauge
Class
75°C
8AWG (8.37mm2)
75°C
10AWG (5.26mm2)
60°C
24AWG (0.204mm2)
60°C
Standard Ethernet cable
Current Rating
63A
30A