in-lite CB-056/M Manual page 15

Hide thumbs Also See for CB-056/M:

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 12
EN
You can make several branches as long as this total does not exceed the
maximum cable length:
14/2 cable up to 40 m (Fig. 8A)
10/2 cable up to 80 m (Fig. 8B)
Does your lighting plan include fixtures with power greater than 35 W?
Always use the 10/2 cable for these.
Important!
The maximum load of each cable connector is 50 W. If the total power of
the fixtures after the CC-2 is greater than 50 W, then multiple CC-2s must
be fitted. (Fig. 10). Always round up the number of cable connectors to be
used. (Fig. 11). Try to spread the power as evenly as possible along the
cable. This will benefit the light output.
Installation tips
Tip 1
Use plenty of cable for the installation. The cable will not then be under
tension if the garden subsides a little.
Tip 2
Insulate the cable ends with caps. You can do this by pulling the end
three centimetres of cable apart and putting a cap on each end. You do
not need to remove any insulation from the cable.
Tip 3
When connecting the fixtures leave plenty of cable from the fixture.
There are special extension cables (CBL-EXT CORD) of 1 metre and 3
metres available to increase the distance of the fixture to the main cable.
These are easy to install between the mini-connector on the fixture and
the mini-connector on the Easy-Lock (Fig. 12).
If after reading these instructions you have further question about
installing 12 V cable, please contact your dealer.