Soap water method
1. Remove the caps from the main service valves
2. Remove the service-port caps from the main service
valves
3. To open the main service valve turn the valve stem
counterclockwise approximately 90°, wait for about 2~3
sec, and close it
4. Apply a soap water or liquid neutral detergent on the
indoor unit connection or outdoor unit connections by a
soft brush for leakage of the connecting points of the
piping
5. If bubbles come out, the pipes have leakage.
Evacuation
1. Connect the charge hose end described in the
preceding steps to the vacuum pump to evacuate
the tubing and indoor unit.
Confirm the "Lo" knob of the manifold valve is
open. Then, run the vacuum pump.
The operation time for evacuation varies with
tubing length and capacity of the pump. The
following table shows the time required for
evacuation. Each pipe of indoors must be
evacuted.
Required time for evacuation when 30 gal/h vacuum
pump is used
If tubing length is less
than 10m (33 ft)
10 min. or more
2. When the desired vacuum is reached, close the
"Lo" knob of the manifold valve and stop the
vacuum pump.
Finishing the job
1. With a service valve wrench, turn the valve stem of
liquid side valve counter-clockwise to fully open the
valve.
2. Turn the valve stem of gas side valve counter-
clockwise to fully open the valve.
3. Loosen the charge hose connected to the gas side
service port slightly to release the pressure, then
remove the hose.
4. Replace the flare nut and its bonnet on the gas side
service port and fasten the flare nut securely with an
adjustable wrench. This process is very important to
prevent leakage from the system.
5. Replace the valve caps at both gas and liquid side
service valves and fasten them tight.
This completes air purging with a vacuum pump.
If tubing length is longer
than 10m (33 ft)
15 min. or more
Air Purging and Evacuation
The air conditioner is now ready to test run.
Gas side
piping
Outdoor unit
Manifold valve
Pressure
gauge
Open
Vacuum pump
Liquid side
piping
Indoor unit
Lo
Hi
Close
Installation Manual 37