Instruction Manual
Form 5300
July 2005
ATEX (LCIE)—TYPE n
SPECIAL CONDITIONS FOR SAFE USE:
THIS EQUIPMENT IS INTRINSICALLY SAFE AND CAN BE USED IN POTENTIALLY
EXPLOSIVE ATMOSPHERES.
THE ELECTRICAL PARAMETERS OF CERTIFIED EQUIPMENT WHICH CAN BE
CONNECTED TO THE DEVICE MUST NOT EXCEED THE FOLLOWING VALUES:
30 Vdc ; I
150 mA ; P
1.25 W
U
0
0
0
AMBIENT TEMPERATURE:
T6, AT T
= 47_C
amb
T5, AT T
= 62_C
amb
T4, AT T
= 82_C
amb
ATEX (LCIE)—INTRINSIC SAFETY
Figure 37. Type 3722 ATEX Approvals Nameplates
3710 and 3720 Positioners
ATEX (KEMA)—FLAMEPROOF
51