Connecting The Purge Tube - Emerson FISHER 3710 Instruction Manual

Converter
Hide thumbs Also See for FISHER 3710:
Table of Contents

Advertisement

Instruction Manual
Form 5300
July 2005
LONG-BLADED SCREW
DRIVER THROUGH VENT
W6073/IL
installs in the vent opening in the positioner base
plate. When the purge tube is used, it relays actuator
exhaust pressure from the positioner into the
actuator housing.
Within the actuator and positioner assembly,
exhaust pressure takes the following course:
D The actuator exhaust pressure vents from the
actuator through the positioner spool valve into the
positioner case.
D The exhaust pressure then exits the positioner
case through the vent opening.
D The purge tube carries the exhaust pressure
into the actuator housing.
D The exhaust pressure then purges the actuator
housing and dissipates from the housing.
Most Fisher actuators do not have vent openings.
The exhaust pressure simply dissipates from within
the actuator housing. However, the Types 1051,
1052, and 1061 actuators feature an operational
screened vent connection when a metal access
plate is specified for the actuator housing.
Figure 13. Mounting the Positioner Base Plate with Purge Tube
3710 and 3720 Positioners
PURGE TUBE (KEY 58)
O-RINGS (KEY 59)
When using the purge option, remember: The
actuator and positioner assembly is not airtight.
However, if you use the optional purge tube to
connect the positioner to the actuator and the
actuator has a vent opening, leave open the 1/4-inch
NPT vent connection in the actuator housing to
prevent pressure buildup in the positioner case.
If the 1/4-inch NPT vent connection is available, a
vent line can be installed from the actuator.
However, the valve/actuator/positioner assembly is
not airtight. Maintain adequate ventilation and
observe other safety measures.
For help in selecting the purge option for positioner/
actuator combinations, contact your Fisher sales
office.

Connecting the Purge Tube

The positioner mounts directly to the actuator cover
plate of Types 1051, 1052, and 1061 actuators. See
table 4 for actuator sizes.
With an integral mounting, a purge tube (key 58),
with two O-rings (key 59), can be used to relay
actuator exhaust pressure from the positioner into
the actuator housing. If the current actuator cover
17