3710 and 3720 Positioners
(1)
Operating Influences
Supply Pressure Sensitivity: A 10% change in
supply pressure changes the valve shaft position
less than the following percentages of valve
rotation:
Type 3710: 1.0% at 4.1 bar (60 psig) supply
pressure
Type 3720: 1.5% at 4.1 bar (60 psig) supply
pressure
Operative Temperature Limits
J
−40 to 80_C (−40 to 180_F), J −50 to 80_C
(−58 to 180_F) or J 0 to 107_C (32 to 225_F)
(Type 3710 only)
Hazardous Area Classification for Type 3710
Type 3710 pneumatic positioners comply with the
requirements of ATEX Group II Category 2 Gas
and Dust
Housing Classification for Type 3722 Converter
NEMA 3 (FM), Enclosure 3 (CSA), IP54 per IEC
60529. Mount instrument with vent on side or
bottom if weatherproofing is a concern.
1. This term is defined in ISA Standard S51.1.
2. For direct action, an increasing input signal extends actuator rod. For reverse action, an increasing input signal retracts actuator rod.
3. Normal cubic meters per hour (0°C and 1.01325 bar absolute). Scfh — standard cubic feet per hour (60°F and 14.7 psia).
4. Typical valves tested using a Fisher Type 1061 size 30 actuator at 4.1 bar (60 psig) supply pressure. Performance may vary with other actuator types and supply pressures.
5. The pressure and temperature limits in the document, and any applicable code or standard limitation should not be exceeded.
Port
Electrostatic Discharge (ESD)
Radiated EM field
Enclosure
Enclosure
Rated power frequency magnetic field
Burst (fast transients)
Surge
I/O signal/control
I/O signal/control
Conducted RF
Specification limit = ±1% of span
1. A = No degradation during testing. B = Temporary degradation during testing, but is self-recovering.
4
Table 1. Specifications (Continued)
(1,5)
Table 2. EMC Immunity Performance Criteria
Phenomenon
Electrical Classifications for Type 3722
Converter
Intrinsically Safe, Explosion proof,
Dust-Ignition proof,
Intrinsically Safe, Explosion proof,
Dust-Ignition proof, Non-incendive
APPROVED
Intrinsically Safe, Flameproof, Type n
SAA
Intrinsically Safe, Flameproof, Type n
ATEX
Refer to tables 5 and 6, and figures 34, 35, 36, 37
and 38 and the Hazardous Area Classification
bulletins 9.2:001 series and 9.2:002 for additional
information and/or approvals.
Pressure Connections
1/4-inch NPT female
Conduit Connection for Type 3722 Converter
J 1/2-inch NPT female (standard) or
J M20 female (optional)
Rotary Valve Rotation
J 90 degrees (standard) J 60 degrees (optional)
Approximate Weight
Type 3710: 2.04 kg (4.5 pounds)
Type 3720: 2.72 kg (6.0 pounds)
Basic Standard
IEC 61000-4-2
IEC 61000-4-3
80 to 1000 MHz, 10 V/m 1 KHz AM at 80%
IEC 61000-4-8
IEC 61000-4-4
IEC 61000-4-5
1 KV (line to ground only)
IEC 61000-4-6
150 kHz to 80 MHz at 3 volts
Instruction Manual
Test Level
4 KV contact 8 KV air
60 A/m at 50 Hz
1 KV
Form 5300
July 2005
Performance
(1)
Criteria
A
A
A
A
B
A