Application SW08020: Pump PID 2 [Advanced Pump PID Control]
Parameters programmed by the Application:
The following parameters are automatically programmed by the 'Application' when it is loaded. They are
listed below for reference purposes only.
Application Menu:
1. "Rated Motor Amps"
B02 = ?
2. " Overload current"
D020 = ?
3. "Rated Motor RPM"
B04 = 1470
4. "Transducer Scale" = 1000 (default)
H09 = 1000
5. "Set Pressure" = 500 kPa
F100 = 50.0
6. "Min. Speed (Hz)" = 0
C01 = 0Hz
7. "Idle Threshold %" = 20
H100 = 20
8. "Time before Idle" = 5
H101 = 5
9. "Resume @ PV" = 25% "Below SV"
H104 = 25%
10. "Low Trip Level" = 250.0 kPa
H110 = 250.0
11. "Low Trip time" = 30Sec
G252 = 30
12. "High Trip Level" = 800 kPa
H111 = 800
13. "Pipe Fill" = DISABLED
H120 = 0
14. " Fill Speed (Hz)" = 40
H123 = 40Hz
15. "Fill to Level" = 300kPa
H122 = 300
16. "Fill Time (s)" = 40
H121 = 40
17. "Low Bore Timeout" =
G070 = 0
Page 18 Document: IM00127 RevB
0 secs
18/04/18
Other Preset Parameters
C030 [Accel] = 1 Sec
C031 [Decel] = 1 sec
C032 [S time] = 0.5 Sec
C033 [Dual Ramp] = Enabled
F010 [Remote Ref] = PID-A Opt
F1001 [PRESET 1 units] = PID A
-High Pressure Trip Config.-
G108 [AI 32,33,Config] = 4-20mA
G230 = [UA1 trip[ Always active
G231 = [UA1 Signal] PVA-Over
G233 = [UA1 msge] HI PRESSURE
-Signal Loss Trip-
G106 [AI 32,34, cmp lo thres] = 2.0 mA
G240 [UA2 Trip] = active with Run cmd
G241 [UA2 Signal] = Lo AI(32,34)
G243 [UA2 msge] = SIGNAL LOST
-Low Pressure trip-
G250 = [UA3 Trip] Active with loop control
G251 = [UA3 Signal] PVA –Under
G253 = [UA3 msge] : LO PRESSURE
-Fill time out trip-
G260 = [UA4 Trip] Run command
G261 = [UA4 Signal] pipe fill timer
G262 = [UA4 Delay] 1 sec
G263 = [UA4 msge] FILL T/O
-Low Bore Customer-
G271 = `TMR 1
G272 = -DRY-
G01 Digital Input Config = CUSTOM
I02 = Logic Block 1
I201 = D2(3)
I202 = TMR 1
I203 = LB1 Logic LLLHLLLH
G071 = [TMR 1 Mode] Delay ON Init.
G0720 = TMR 1 IN2 = ON
G0721 = TMR 1 IN1 = D4(37)
-PID Config.-
H01 [Proportional Band] =200%
H02 = [ Integrator time] = 2.00
H06 = [PID-A SV] = PRESET 1
H07 = [PID-A PV] = AI(32,34]
H08 = PID-A units] = kPa
H102 = Resume by PV threshold
H107 [No Flow Sw] = ~D3(35)
J02 = [Display] = PID Display