Electrical Connections; General - Nibe F1345 Series Installer Manual

Ground source heat pump
Hide thumbs Also See for F1345 Series:
Table of Contents

Advertisement

5 Electrical connections

General

All electrical equipment, except the outdoor sensors,
room sensors and the current sensors are ready connec-
ted at the factory.
For 40 and 60 kW, the brine pump is enclosed (does not
apply to all countries, see list of enclosed items) and
must be installed outside the heat pump.
• Disconnect the heat pump before insulation testing
the house wiring.
• If the building is equipped with an earth-fault breaker,
each F1345 should be equipped with a separate one.
• If a miniature circuit breaker is used this should have
at least motor characteristic "C". See
size.
• Electrical wiring diagram for the heat pump, see
53.
• Communication and sensor cables to external connec-
tions must not be laid close to high current cables.
• The minimum area of communication and sensor
cables to external connections must be 0.5 mm² up
to 50 m, for example EKKX or LiYY or equivalent.
• When cable routing in F1345, cable grommets (e.g.
UB2, power cables and UB3, signal cables, marked in
image) must be used. Secure the cables in the grooves
in the panel using cable ties (see image).
NOTE
The switch (SF1) must not be moved to "" or
"
" until the boiler has been filled with water.
Components in the product could be damaged.
NIBE F1345
page 46
for fuse
page
FC1
MINIATURE CIRCUIT-BREAKER
The heat pump operating circuit and some of its internal
components are internally fused by a miniature circuit
breaker (FC1).
Miniature circuit-breakers (EP14-FC1) and (EP15-FC1)
cut the power to the relevant compressor if the current
is too high.
NOTE
Electrical installation and service must be car-
ried out under the supervision of a qualified
electrician. Cut the current with the circuit
breaker before carrying out any servicing.
Electrical installation and wiring must be carried
out in accordance with the stipulations in force.
NOTE
Check the connections, main voltage and phase
voltage before the machine is started, to pre-
vent damage to the heat pump electronics.
NOTE
Refer to the outline diagram of your system
for positioning of the temperature sensor.
FC1
UB2
UB3
EP15
EP14
Chapter 5 | Electrical connections
23