Altronix SMP3CTX Series Manual

Altronix SMP3CTX Series Manual

Advertisement

Quick Links

SMP3CTX Series Power Supply Configuration Reference Chart:
SMP3CTX
SMP3PMCTX
SMP3PMCTXX
SMP3PMP4
SMP3PMP4CB
SMP3PMP8
SMP3PMP8CB
SMP3PMP16
SMP3PMP16CB
These units will convert a 115VAC / 60Hz input, into a regulated 12VDC or 24VDC output up 2.5 amp of
continuous load current (see specifications).
• Maximum charge current .5 amp.
• Filtered and electronically regulated outputs.
• Built-in charger for sealed lead acid or gel type batteries.
• Automatic switch over to stand-by battery when
AC fails (zero voltage drop).
• AC input and DC output LED indicators.

Power Supply Voltage Output Specifications: *

Output VDC
12VDC
SW1 - Closed (Fig. 1B, pg. 3)
24VDC
SW1 - Open (Fig. 1B, pg. 3)
*Specified at 25˚ C ambient.

Installation Instructions:

The unit should be installed in accordance with The National Electrical Code and all applicable Local Regulations.
1. Mount the unit in desired location.
2. Set SW1 on the power supply board to the desired DC output voltage
(power supply voltage output specification chart).
3. Connect AC power to terminals marked [L & N], connect ground to terminal marked [G] (if used).
Use 18 AWG or larger for all power connections (Battery, DC output).
Use 22 AWG to 18 AWG for power limited circuits (AC Fail/Low Battery reporting).
Keep power limited wiring low battery, AC fail separate from non-power limited wiring
(115VAC / 60Hz Input, Battery Wires, DC Output). Minimum .25" spacing must be provided.
SMP3CTX Series
-
1
-
-
-
1
-
-
-
1
-
-
PD4
4
x
-
PD4CB
4
-
x
PD8
8
x
-
PD8CB
8
-
x
PD8
16
x
-
PD8CB
16
-
x
Switch Position
-
-
.65
2.5
-
x
.65
2.5
-
x
.65
2.5
3.5
x
.65
2.5
2.5
x
.65
2.5
3.5
x
.65
2.5
2.5
x
.65
2.5
3.5
x
.65
2.5
2.5
x
.65
2.5

Overview:

Specifications:

• Short circuit and thermal overload protection.
• Complete with power supply, power distribution module
(when applicable), enclosure, cam lock & battery leads.
• Power on-off switch.
Supervised models only:
• AC fail supervision (form "C" contacts).
• Low battery supervision (form "C" contacts).
Max. Load DC
2.5 amp
2.5 amp
- 1 -

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SMP3CTX Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Altronix SMP3CTX Series

  • Page 1 SMP3CTX Series SMP3CTX Series Power Supply Configuration Reference Chart: SMP3CTX SMP3PMCTX SMP3PMCTXX SMP3PMP4 PD4CB SMP3PMP4CB SMP3PMP8 PD8CB SMP3PMP8CB SMP3PMP16 SMP3PMP16CB PD8CB Overview: These units will convert a 115VAC / 60Hz input, into a regulated 12VDC or 24VDC output up 2.5 amp of continuous load current (see specifications).
  • Page 2 4. Connect devices to be powered: a. For Power Supply Board connect to terminals marked [+ DC -]. b. For Power Distribution Module(s) connect devices to be powered to terminal pairs 1 to 4 marked [1P & 1N thru 4P & 4N] (Fig. 2, pg. 3) or 1 to 8 marked [1P & 1N thru 8P & 8N] (Fig. 3, pg. 3) carefully observing correct polarity.
  • Page 3 Fig. 1 CAUTION: De-energize unit prior to servicing. For continued protection against fire hazard replace fuse with the same type and rating 3.5A, 250V. Replace protective cover on the fuse of the power supply board, before energizing unit. Fuse Cover Wire Green Strap...
  • Page 4 3.68" 2.25" 4.56" Altronix is not responsible for any typographical errors. Product specifications are subject to change without notice. Altronix Corp. 140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056 web site: www.altronix.com, e-mail: info@altronix.com, Made in U.S.A.

This manual is also suitable for:

Smp3pmctxSmp3pmctxxSmp3pmp4Smp3pmp4cbSmp3pmp8Smp3pmp8cb ... Show all

Table of Contents