Table ED-2 — Unit Wiring With Electric Heat Single Point Connection — 380–415 Volts
Unit
Heater
Model No.
Model No.
BAYHTRR412A
WSC060AD
BAYHTRR418A
BAYHTRR423A
BAYHTRS418A
WSC072AD
BAYHTRS427A
BAYHTRS436A
BAYHTRS418A
WSC090AD
BAYHTRS427A
BAYHTRS436A
BAYHTRT427A
WSC120AD
BAYHTRT436A
BAYHTRT454A
Notes:
1. All units to be installed under local codes
2. kW shown for 380V / 415V
Table ED-3 — Unit Wiring With Electric Heat Single Point Connection — 200 Volts
Unit
Heater
Model No.
Model No.
BAYHTRR312AA
WSC060AT
BAYHTRR318AA
BAYHTRR323AA
BAYHTRS318AA
WSC072AT
BAYHTRS327AA
BAYHTRS336AA
BAYHTRS318AA
WSC090AT
BAYHTRS327AA
BAYHTRS336AA
BAYHTRT327AA
WSC120AT
BAYHTRT336AA
BAYHTRT354AA
Notes:
1. All units to be installed under local codes
2. kW shown for 380V / 415V
36
Electrical
Data
2
Heater
Control
kW Rating
MBH
Stages
380 / 415 Volts
7.5 / 9.0
26 / 31
2
10.9 / 13.0
38 / 45
2
14.4 / 17.2
50 / 59
2
11.3 / 13.5
39 / 47
1
16.9 / 20.2
58 / 69
2
22.6 / 26.9
78 / 92
2
11.3 / 13.5
39 / 47
1
16.9 / 20.2
58 / 69
2
22.6 / 26.9
78 / 92
2
16.9 / 20.2
58 / 69
2
22.6 / 26.9
78 / 92
2
33.9 / 40.4
116 / 138
2
Heater
2
Control
kW Rating
MBH
Stages
200 Volts
8.3
28
2
12.1
41
2
16.0
55
2
12.5
43
1
18.8
64
2
25.0
85
2
12.5
43
1
18.8
64
2
25.0
85
2
18.8
64
2
25.0
85
2
37.5
123
2
Standard Indoor Fan Motor
Minimum
Maximum Fuse
Minimum
Circuit
Size Or Maximum
1
Ampacitiy
Circuit Breaker
Ampacitiy
33.3 / 34.6
40 / 40
39.7 / 41.6
45 / 45
46.3 / 48.8
50 / 50
43.4 / 45.4
50 / 50
44.4 / 46.4
54.1 / 57.1
60 / 60
55.1 / 58.1
64.8 / 68.7
70 / 70
65.8 / 69.7
46.3 / 48.3
50 / 50
48.0 / 50.0
56.9 / 59.9
60 / 60
58.6 / 61.6
67.7 / 71.6
70 / 70
69.4 / 73.3
63.3 / 66.3
70 / 70
74.0 / 77.9
80 / 80
95.5 / 101.4
100 / 110
Standard Indoor Fan Motor
Minimum
Maximum Fuse
Minimum
Circuit
Size Or Maximum
Ampacitiy
Circuit Breaker
1
Ampacitiy
67.2
80
80.9
90
95.0
100
86.4
100
109.1
110
131.5
150
92.7
100
115.4
125
137.8
150
127.4
150
149.7
150
194.9
200
Oversized Indoor Fan Motor
Maximum Fuse
Circuit
Size Or Maximum
1
Circuit Breaker
50 / 50
60 / 60
70 / 70
50 / 50
60 / 60
70 / 70
Oversized Indoor Fan Motor
Maximum Fuse
Circuit
Size Or Maximum
Circuit Breaker
1
89.1
100
111.8
125
134.2
150
95.3
100
118.0
125
140.4
150
PKGP-PRC004-EN