Condensate Drain Piping - Trane WCY024G1 Installation, Operation & Maintenance Manual

Single package heat pump 13-14 seer convertible 2 - 5 ton
Table of Contents

Advertisement

w
WEATHERPROOF
UNIT DUCT
FLANGE
FIELD DUCT
UNIT EXTERIOR
UNIT DUCT FLANGE
WEATHERPROOF
THIS SEAM
FIELD DUCT
UNIT EXTERIOR
WEATHERPROOF
THIS SEAM
UNIT DUCT
FLANGE
FIELD DUCT
HORIZONTAL
A 3/4-inch female NPT condensate drain connection is pro-
vided on the evaporator access panel end of the unit. See
Figure 4. Provide a trap and fill it with water before starting the
unit to avoid air from being drawn through. Follow local codes
and standard piping practices when running the drain line.
Pitch the line downward away from the unit. Avoid long
horizontal runs. See Figure 13.
NOTE: Do not use reducing fittings in the drain lines. The
condensate drain must be:
Made of 3/4" pipe size.
Pitched 1/4" per foot to provide free drainage to
convenient drain system.
Trapped.
Must not be connected to closed drain system.
DUCT ATTACHMENT METHODS
AIR PROOF
THIS SEAM
UNIT EXTERIOR
FIELD DUCT
THIS SEAM
UNIT DUCT
FLANGE

CONDENSATE DRAIN PIPING

UNIT BASE
UNIT DUCT
FLANGE
AIR PROOF
THIS SEAM
UNIT DUCT
UNIT BASE
NOT RECOMMENDED
FIELD DUCT
DOWNFLOW
The following warning complies with State of California law, Proposition 65.
WARNING:
fiberglass wool insulation! Fiberglass dust and ceramic
fibers are believed by the State of California to cause
cancer through inhalation. Glasswool fibers may also
cause respiratory, skin, or eye irritation.
e
TYPICAL CONDENSATE DRAIN PIPING
3
/
" PVC OR COPPER
4
TUBING AND FITTINGS
1-1/2"
MIN.
AIR PROOF
THIS SEAM
FIELD
DUCT
UNIT DUCT FLANGE
UNIT BASE
FLANGE
WATERPROOF SEAM
FIELD DUCT
This product contains
UNIT BASE
WITH BUTYL OR
SILICONE
Page 11

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Wcy060g1Wcy030g1Wcy036g1Wcy042g1Wcy048g1

Table of Contents