Table ED-8. Single Stage, Low kW Electric Heat (Digit 18 = V)
Unit Size
Voltage
02
208/60/1
240/60/1
277/60/1
03
208/60/1
240/60/1
277/60/1
208/60/3
240/60/3
480/60/3
04
208/60/1
240/60/1
277/60/1
208/60/3
240/60/3
480/60/3
06
208/60/1
240/60/1
277/60/1
208/60/3
240/60/3
480/60/3
08
208/60/1
240/60/1
277/60/1
208/60/3
240/60/3
480/60/3
10
208/60/1
240/60/1
277/60/1
208/60/3
240/60/3
480/60/3
12
208/60/1
240/60/1
277/60/1
208/60/3
240/60/3
480/60/3
Note: All data based on individual units. Electric heat will operate only with fan at high speed.
CAB-PRC001-EN
Electrical Data
Table ED-7. Single-Stage, Max kW Electric Heat (Digit 18 = N)
Unit
Size
Volts
Hz
208
240
02
277
60
208
240
480
208
240
03
277
60
208
240
480
208
240
04
277
60
208
240
480
208
240
06
277
60
208
240
480
Note: All data based on individual units. Electric heat will operate only with fan at high speed.
# Wires
kW
Amps/ph
2
0.75
3.7
2
1.0
4.2
2
1.0
3.7
2
2.25
10.9
2
3.0
12.5
2
3.0
10.9
3
2.25
6.3
3
3.0
7.3
4
3.0
3.7
2
2.25
10.9
2
3.0
12.5
2
3.0
10.9
3
2.25
6.3
3
3.0
7.3
4
3.0
3.7
2
2.25
10.9
2
3.0
12.5
2
3.0
10.9
3
2.25
6.3
3
3.0
7.3
4
3.0
3.7
2
2.25
10.9
2
3.0
12.5
2
3.0
10.9
3
2.25
6.3
3
3.0
7.3
4
3.0
3.7
2
2.25
10.9
2
3.0
12.5
2
3.0
10.9
3
2.25
6.3
3
3.0
7.3
4
3.0
3.7
2
2.25
10.9
2
3.0
12.5
2
3.0
10.9
3
2.25
6.3
3
3.0
7.3
4
3.0
3.7
Heater
Ph
Wires
kW
1
2
2.25
1
2
3.0
1
2
3.0
3
3
2.25
3
3
3.0
3
4
3.0
1
2
4.5
1
2
6.0
1
2
6.0
3
3
4.5
3
3
6.0
3
4
6.0
1
2
5.7
1
2
7.5
1
2
7.5
3
3
5.7
3
3
7.5
3
4
7.5
1
2
7.9
1
2
10.5
1
2
10.5
3
3
7.9
3
3
10.5
3
4
10.5
kW
Amps/ph
1.5
7.3
2.0
8.4
2.0
7.3
3.3
15.9
4.5
18.8
4.5
16.3
3.3
9.2
4.5
10.9
4.5
5.5
3.3
15.9
4.5
18.8
4.5
16.3
3.3
9.2
4.5
10.9
4.5
5.5
3.3
15.9
4.5
18.8
4.5
16.3
3.3
9.2
4.5
10.9
4.5
5.5
3.3
15.9
4.5
18.8
4.5
16.3
3.3
9.2
4.5
10.9
4.5
5.5
Heater
Amps/ph
10.9
12.5
10.9
6.3
7.3
3.7
21.7
25.0
21.7
12.6
14.5
7.3
27.5
31.3
27.1
15.9
18.1
9.1
38.0
43.8
38.0
21.9
25.3
12.7
kW
Amps/ph
4.5
21.7
6.0
25.0
6.0
21.7
4.5
12.5
6.0
14.5
6.0
7.3
5.7
27.5
7.5
31.3
7.5
27.1
5.7
15.9
7.5
18.1
7.5
9.1
6.6
31.8
9.0
37.5
9.0
32.5
6.6
18.4
9.0
21.7
9.0
10.9