Heating performance is based on 70 F (21 C) entering air temperature, 2 psig (14 kPa) and 5 psig (103 kPa) entering steam pressure.
All performance measured on high speed tap, zero ESP , no filter.
Table PD-10. High Static Motor, Group 1
Unit
CFM
Size
Coil
(L/s)
2
Steam
208 (132)
3
Steam
358 (169)
4
Steam
393 (185)
6
Steam
658 (311)
8
Steam
901 (425)
10
Steam
1110 (524)
12
Steam
1264 (597)
Table PD-11. High Static Motor, Group 2
Unit
CFM
Size
Coil
(L/s)
2
Steam
251 (119)
3
Steam
326 (154)
4
Steam
364 (172)
6
Steam
603 (285)
8
Steam
829 (392)
10
Steam
1024 (483)
12
Steam
1171 (553)
Table PD-12. Steam Properties
Steam Pressure PSIG (kPa)
Sat. Steam Temp. F (C)
Latent Heat — BTU/LB. (kJ/kg)
965 (2240)
Note:
Q/ITD = MBH (kW)/(Saturated Steam temperature - Entering air temperature) when DT and GPM remain constant. To determine heating capacities at a different saturated steam or entering
air temperature, compute the new ITD and multiply it by the Q/ITD shown.steam pressure. All performance measured on high speed tap, zero ESP , with a throwaway filter.