Heating performance is based on 70 F (21 C) entering air temperature, 180 F (82 C) entering hot water temperature with a 30 F (-1 C)
∆T. All performance measured on high speed tap, zero ESP, and a throwaway filter.
Table PD-4. Free Discharge Motor, Group 3
Unit
CFM
Size
Coil
(L/s)
2
2H
198 (93)
3H
188 (90)
4H
177 (84)
3
2H
262 (124)
3H
260 (123)
4H
242 (114)
4
2H
330 (156)
3H
320 (151)
4H
304 (144)
6
2H
512 (242)
3H
508 (240)
4H
483 (228)
8
2H
665 (314)
3H
623 (294)
4H
596 (282)
10
2H
829 (391)
3H
835 (394)
4H
796 (376)
12
2H
940 (444)
3H
923 (436)
4H
876 (413)
Note:
1. CFM = Cubic feet per minute
2. TMBH = Total capacity (MBH)
3. GPM = Gallons per minute
4. WPD = Water pressure drop (feet of water)
5. Q/ITD = MBH (kW)/(Entering water temperature - Entering air temperature) when DT and GPM (L/s) remain constant. To determine heating capacities at a different entering water
temperature or entering air temp, compute the new ITD and multiply it by the Q/ITD shown.
6. Medium and low speed capacities are approximately 80 percent and 60 percent respectively of the high speed capacity.