Heating performance is based on 70 F (21 C) entering air temperature, 2 psig (14 kPa) and 5 psig (103 kPa) entering steam pressure.
All performance measured on high speed tap, zero ESP , with a throwaway filter.
Table PD-7. Free Discharge Motor, Group 1
Unit
CFM
Size
Coil
(L/s)
2
Steam
234 (110)
3
Steam
311 (147)
4
Steam
383 (181)
6
Steam
601 (284)
8
Steam
783 (370)
10
Steam
974 (460)
12
Steam
1104 (521)
Table PD-8. Free Discharge Motor, Group 2
Unit
CFM
Size
Coil
(L/s)
2
Steam
207 (98)
3
Steam
277 (130)
4
Steam
346 (163)
6
Steam
538 (254)
8
Steam
702 (331)
10
Steam
875 (413)
12
Steam
993 (469)
Table PD-9. Free Discharge Motor, Group 3
Unit
CFM
size
Coil
(L/s)
2
Steam
195 (92)
3
Steam
259 (122)
4
Steam
328 (155)
6
Steam
507 (239)
8
Steam
662 (312)
10
Steam
827 (390)
12
Steam
938 (443)
Note:
Q/ITD = MBH (kW)/(Saturated Steam temperature - Entering air temperature) when DT and GPM remain constant. To determine heating capacities at a different saturated steam or
entering air temperature, compute the new ITD and multiply it by the Q/ITD shown.