Download Print this page

ABB ACQ580-P Series Supplement Installation Manual page 15

Packaged drives with disconnect 1...60 hp
Hide thumbs Also See for ACQ580-P Series:

Advertisement

Supplemental Installation Manual for ACQ580-Px
575 Volt
Output Range
1, 2
Type Code
A
Px
ACQ580-
-02A7-6
2.7
Px
ACQ580-
-03A9-6
3.9
Px
ACQ580-
-06A1-6
6.1
Px
ACQ580-
-09A0-6
9
Px
ACQ580-
-011A-6
11
Px
ACQ580-
-017A-6
17
Px
ACQ580-
-022A-6
22
Px
ACQ580-
-027A-6
27
Px
ACQ580-
-032A-6
32
1) "Px" represents both PCand PD.
2) PC is rated 600Y/347V unless otherwise specified. For use on a solidly grounded Wye source only.
3) PC supports Delta network configuration.
Maximum Power Wiring Data
Base
Circuit
Drive
Breaker
Disconnect
Frame
UL
Switch UL
HP
Size
(NEMA)
(NEMA) Type
Type 1
1 and 12
and 12
#10
2
R2
62 in-lbs
#12
3
R2
62 in-lbs
55 in-lbs
5
R2
#10
7.5
R2
62 in-lbs
10
R2
15
R2
#6
62 in-lbs
55 in-lbs
20
R3
25
R3
#4
62 in-lbs
55 in-lbs
30
R3
Ground
Lugs
Motor
UL (NEMA)
Terminals
Type 1
and 12
#10
#6
1.1 ft-lbs
#6
#2
50 in-lbs
#2
2.6 ft-lbs
#4
ACQ580-PC/PD
15

Advertisement

loading

This manual is also suitable for:

Acq580-pcAcq580-pdAcq580-pd seriesAcq580-pc series