Download Print this page

ABB ACQ580-P Series Supplement Installation Manual page 13

Packaged drives with disconnect 1...60 hp
Hide thumbs Also See for ACQ580-P Series:

Advertisement

Supplemental Installation Manual for ACQ580-Px
Power connection terminals
The following tables show maximum wire size and required tightening torque for
incoming power, grounding and motor terminals.
Output
208/230 Volt
Ratings
1
Type Code
A
ACQ580-Px-04A6-2
4.6
ACQ580-Px-06A6-2
6.6
ACQ580-Px-07A5-2
7.5
ACQ580-Px-10A6-2
10.6
ACQ580-Px-017A-2
16.7
ACQ580-Px-024A-2
24.2
ACQ580-Px-031A-2
30.8
ACQ580-Px-046A-2
46.2
ACQ580-Px-059A-2
59.4
ACQ580-Px-075A-2
74.8
1)
"Px" represents both PC and PD.
1)"Px" represents both PC and PD.
Maximum Power Wiring Data
Base
Circuit
Disconnect
Drive
Breaker
Frame
UL
HP
Size
UL (NEMA)
(NEMA)
Type 1
and 12
1
R1
1.5
R1
#10
62 in-lbs
55 in-lbs
2
R1
3
R1
5
R1
#6
62 in-lbs
55 in-lbs
7.5
R2
#4
10
R2
62 in-lbs
55 in-lbs
#2
15
R3
62 in-lbs
55 in-lbs
#1
20
R3
62 in-lbs
55 in-lbs
#1/0
25
R4
62 in-lbs
55 in-lbs
Switch
Ground Lugs
Motor
UL (NEMA)
Terminals
Type 1
Type 1 and 12
and 12
#10
#10
0.7 ft-lbs
#6
#6
50 in-lbs
#4
1.1 ft-lbs
#2
#2
2.6 ft-lbs
#1
#1/0
#1
3.0 ft-lbs
ACQ580-PC/PD
13
#2

Advertisement

loading

This manual is also suitable for: