Hydraulic Connection / Electrical Connection - Wolf ZP-3 Installation Instructions Manual

Freshwater module/ dhw circulation pump set
Table of Contents

Advertisement

Available languages

Available languages

Electrical connection
Hydraulic connection
Connections A = cold water, 1" female thread
B = DHW, 1" female thread
C = from buffer, 1" male thread
D = to buffer, 1" male thread
E = DHW circulation, ½" female thread (op-
tional)
F = flushing connection, ¾" male thread
Main compo-
1 = plate heat exchanger
nents
2 = bypass pipe for admixing from centre
zone
3 = push-fit connection for DHW circulation
unit
4 = primary pump Yonos PARA HU 25/7.0
PWM 1W
5 = PT1000 temperature sensor
6 = mixing valve with servomotor
7 = freshwater module controller
8 = DHW sensor
9 = optimum DHW circulation unit with pump
and electronic return thermostat (for pul-
sed or timed operation)
3065014_201612
Hydraulic connection /
electrical connection
The system's internal electrical components have been wired at the factory. Connect the
system to the mains (230 V/AC, 50 - 60 Hz) using the attached power cable. Any work
performed on energised parts of the module must be carried out exclusively in accor-
dance with the requirements of the power supply utility and relevant current standards
and regulations. Correct earthing for the FWS-2-80 is provided at the mounting lug.
Protect the drinking water side of the freshwater module against excess pressure
using a safety valve rated to ≤ 10 bar. A drinking water expansion vessel can also
be used as an alternative.
Connect the pipework as shown in the adjacent diagram. When using galvanised pipes
and fittings, observe the installation procedure for preventing electrochemical corrosion.
Tighten flat gasket connections only after the pipes have been sealed in. The pipework
to and from the cylinder, for example when mounting the FWS-2-80 on the wall, must
be sized no less than Cu 28.
Keep lines as short as possible.
CAUTION!
Avoid applying any torque or forces to prefitted components and connection points of
the module.
9
E
4
8
B
5
C
F
3
A D
F
6
7
2
1
33

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fws-2-80

Table of Contents