The calculations are based on the maximum machine current
(see electrical data tables).
For the accessory system the following standardised instal-
lation methods are used, in accordance with IEC 60364,
table 52C:
No. 17: suspended aerial lines, and No. 61: buried conduit
with a derating coefficient of 20.
The calculation is based on PVC or XLPE insulated cables
with copper or aluminium core. The maximum temperature
is 48°C. The given wire length limits the voltage drop to < 5%.
IMPORTANT: Before connection of the main power cables
(L1 - L2 - L3) on the terminal block, it is imperative to
check the correct order of the 3 phases before proceeding
to the connection on then terminal block or the main
disconnect/isolator switch.
The current values used are given for a unit equipped with
a hydronic kit operating at maximum current.
7.4.1 - power cable entry
The power cables can enter the 30RB control box from
below or from the unit side.
Unit raised from the ground (e.g. installation on support
rails): It is recommended to enter the power cables from
below the control box. A removable aluminium plate
below the control box allows introduction of the cables.
Unit placed on the ground (e.g. on a concrete base): It is
recommended to enter the power cables from the
control box side. An aluminium plate on the control box
face allows introduction of the cables. It is important to
check that the power cable bend radius is compatible
with the connection space available in the control box.
Refer to the certified dimensional drawing for the unit.
Table of minimum and maximum wire sections (per phase) for connection to 30RB units
Max. connectable section per phase Min. wire section per phase
30RB Section, mm²
162
1 x 240 or 2 x 150
182
1 x 240 or 2 x 150
202
1 x 240 or 2 x 150
232
1 x 240 or 2 x 150
262
1 x 240 or 2 x 150
302
2 x 240
342
2 x 240
372
2 x 240
402
2 x 240
432
3 x 240
3 x 240
462
522
3 x 240
Circuit a
Circuit B
Circuit C
602
2 x 240
2 x 240
2 x 185
672
2 x 240
2 x 240
2 x 185
732
3 x 240
3 x 240
2 x 185
802
3 x 240
3 x 240
2 x 185
22
Section, mm²
1 x 50
1 x 50
1 x 70
1 x 70
1 x 95
1 x 120
1 x 120
1 x 150
1 x 185
1 x 185
1 x 240
2 x 95
Circuit a
Circuit B
Circuit C
1 x 185
1 x 185
1 x 70
1 x 185
1 x 185
1 x 95
2 x 95
2 x 95
1 x 70
2 x 95
2 x 95
1 x 95
7.4.2 - Connection extension box
This accessory permits stripping the power cables before they
enter the control box, and must be used when the cable bend
radius is not compatible with the connection space available
in the control box. The accessory connection extension box
ensures mechanical protection of the stripped cable, before it
enters the control box. It must be used in the following cases:
Unit placed on the ground and use of power cables
with protective metallic armour.
Unit placed on the ground and use of power cables
with a section > 250 mm
Supply cable inlet

7.5 - Field control wiring

Refer to the 30RB Pro-Dialog Plus Controls IOM and the
certified wiring diagram supplied with the unit for the field
control wiring of the following features:
Customer interlock (safety chain)
Evaporator pump interlock (mandatory)
Remote on/off switch
Remote heat/cool switch
Demand limit external switch 1
Remote dual set point
Alarm, alert and operation report
Evaporator pump control
Heat reclaim condenser pump control (option)
Setpoint reset via outside air temperature sensor reset
(0-10 V)
Various interlocks on the Energy Management Module
(EMM) board (accessory or option)
Max. wire section per phase
Max length,
Wire type
Section, mm² Max. length,
m
180
XLPE Copper
2 x 70
180
XLPE Copper
2 x 70
215
XLPE Copper
2 x 95
205
XLPE Copper
2 x 95
178
XLPE Copper
2 x 95
197
XLPE Copper
2 x 120
185
XLPE Copper
2 x 150
188
XLPE Copper
2 x 185
190
XLPE Copper
2 x 240
190
XLPE Copper
2 x 240
205
XLPE Copper
3 x 185
190
XLPE Copper
3 x 240
190/155
XLPE Copper
2 x 185/2 x 95 430/325
190/178
XLPE Copper
2 x 185/2 x
150
190/155
XLPE Copper
3 x 185/2 x 95 490/325
190/178
XLPE Copper
3 x 185/2 x
150
.
2
Wire type
m
225
XLPE Aluminium
225
XLPE Aluminium
260
XLPE Aluminium
260
XLPE Aluminium
260
XLPE Aluminium
280
XLPE Aluminium
300
XLPE Aluminium
315
XLPE Aluminium
330
XLPE Aluminium
330
XLPE Aluminium
395
XLPE Aluminium
415
XLPE Aluminium
XLPE Cu/XLPE Al
430/375
XLPE Cu/XLPE Al
XLPE Cu/XLPE Al
490/375
XLPE Cu/XLPE Al