4.0 Maintenance and Troubleshooting

The following information is provided to help you keep your MS-PE Series inverter/charger in
optimum operational condition.
4.1

Recommended Inverter and Battery Care

The MS-PE Series inverter/ charger is designed to provide you with years of trouble-free service.
Even though there are no user-serviceable parts, it is recommended that every 6 months you
perform the following maintenance steps to ensure optimum performance and extend the life of
your batteries.
WARNING: Prior to performing the following checks, switch OFF both the AC and DC
circuits.
Visually inspect the batteries for cracks, leaks, or swelling—replace if necessary.
Use baking soda to clean and remove any electrolyte spills or buildups.
Check and tighten all battery hold down clamps (if applicable).
Clean and tighten all battery terminals and connecting cables [10 to 12 ft lbf
(13.6 to 16.3 N-m)].
Check and fi ll battery water levels (Liquid Lead Acid batteries only).
Check individual battery voltages (load test those that have a voltage difference of more than
0.3 VDC from each other)—replace if necessary.
Check all cable runs for signs of chafi ng—replace if necessary.
Check the inverter's cooling vents—clean as necessary.
Check and tighten the inverter's internal AC terminal block connections [16 in lbf (1.8 N-m)].
4.2

Storage for Mobile Installations

When placing the boat or caravan into storage, it is recommended that you perform the following
to ensure the system is properly shut down (or properly confi gured for storage). This is especially
important for maintaining the batteries.
Perform the recommended maintenance steps listed in Section 4.1.
Fully charge the batteries.
Connect AC power (if available) and verify the breaker to the inverter's input is switched ON
(to allow battery charging).
Verify the inverter is switched OFF.
Switch OFF all unnecessary AC and DC loads.
Disable the AGS (if installed) when the boat or caravan is in a confi ned storage area.
WARNING: If an AGS were to start and run the generator for an extended period
of time in a confi ned area, a potentially fatal level of carbon monoxide (CO) could
accumulate.