B-5
Simultaneous Welding and Auxiliary Power
Loads
The previous auxiliary power ratings are with no weld-
ing load. Simultaneous welding and power loads are
specified in the following table. The permissible cur-
rents shown assume that current is being drawn from
either the 120 VAC or 240 VAC supply (not both at the
same time).
Welding
Output Range
Setting
0
50
100
150
210
* Each duplex receptacle is limited to 20 amps.
** Not to exceed 25 A per 120 VAC branch circuit when splitting the 240 VAC output.
(Use the shortest length extension cord possible sized per the following table.)
Current
Voltag
Load
(Amps)
eVolts
(Watts)
15
120
1800
20
120
2400
15
240
3600
20
240
4800
25
240
6000
OPERATION
Ranger 200 Simultaneous Welding and Power Loads
Permissibl Power Watts
(Unity Power Factor)
6000
4500
3000
1500
0
Ranger 200 Extension Cord Length Recommendations
Maximum Allowable Cord Length in ft. (m) for Conductor Size
14 AWG
12 AWG
30
(9)
40
(12)
30
(9)
60
(18)
75
(23)
60
(18)
Conductor size is based on manimum 2.0% voltage drop.
RANGER 200
Permissible
Current in
@120 VAC *
40*
38*
25
12.5
0
10 AWG
8 AWG
75
(23)
125
(38)
50
(15)
88
(27)
150
(46)
225
(69)
100
(30)
175
(53)
90
(27)
150
(46)
Auxiliary
Amps
@ 240 VAC
25
18.8
12.5
6.3
0
6 AWG
4 AWG
175
(53)
300
(91)
138
(42)
225
(69)
350
(107)
600
(183)
275
(84)
450
(137)
225
(69)
250
(76)
B-5