Settings; Operation Principle - ABB Relion 670 Series Communication Protocol Manual

Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 7
LON Functions
Name
INPUT12
INPUT13
INPUT14
INPUT15
INPUT16
Table 17:
Name
ERROR
7.2.5

Settings

Table 18:
MULTICMDRCV Non group settings (basic)
Name
tMaxCycleTime
tMinCycleTime
Mode
tPulseTime
Table 19:
MULTICMDSND Non group settings (basic)
Name
tMaxCycleTime
tMinCycleTime
7.2.6

Operation principle

There are 10 instances of the MULTICMDSND function block. The first two are fast (8 ms cycle
time) while the others are slow (100 ms cycle time). Each instance has 16 binary inputs, to
which 16 independent signals can be connected. Connected signals are sent through
MULTICMDSND to the receiving equivalent, MULTICMDRCV, located on a different IED.
The MULTICMDRCV function block has 16 binary outputs, all controlled through the command
block of one or many MULTICMDSND function blocks. There are 60 instances of the
MULTICMDRCV where the first 12 are fast (8 ms), and the others are slow (100 ms).
Additionally, the MULTICMDRCV has a supervision function, which sets the output connector
"VALID" to 0 (zero) if its block does not receive any data within the time defined by
tMaxCycleTime.
LON connections are established using LON network tool (LNT).
42
Type
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
MULTICMDSND Output signals
Type
BOOLEAN
Values (Range)
Unit
0.050 - 200.000
s
0.000 - 200.000
s
Steady
-
Pulsed
0.000 - 60.000
s
Values (Range)
Unit
0.000 - 200.000
s
0.000 - 200.000
s
© Copyright 2017 ABB. All rights reserved
Default
Description
0
Input 12
0
Input 13
0
Input 14
0
Input 15
0
Input 16
Description
MultiSend error
Step
Default
0.001
11.000
0.001
0.000
-
Steady
0.001
0.200
Step
Default
0.001
5.000
0.001
0.000
1MRK 511 395-UEN E
PID-399-OUTPUTSIGNALS v10
Description
Maximum cycle time between
receptions of input data
Minimum cycle time between
receptions of input data
Mode for output signals
Pulse length for multi command
outputs
Description
Maximum time interval between
transmission of output data
Minimum time interval between
transmission of output data
LON, 670 series
Communication protocol manual
SEMOD119927-1 v2
PID-400-SETTINGS v10
PID-399-SETTINGS v10
M14793-3 v3