Local application factors
* This FTC3 is designed to connect Mr.Slim/Ecodan inverter outdoor unit of MITSUBISHI ELECTRIC to local systems. Please check the following when designing
the local system.
* MITSUBISHI ELECTRIC does not take any responsibility for the local system design.
Heat exchanger
(1) Withstanding pressure
Designed pressure of outdoor unit is 4.15 MPa. Following must be satisfi ed for burst pressure of connecting application.
Burst pressure: More than 12.45 MPa (3 times more than designed pressure)
(2) Performance
Secure the heat exchanger capacity which meets the following conditions. If the conditions are not met, it may result in malfunction caused by the protection
operation or the outdoor unit may be turned off due to the operation of protection system.
1. Evaporate temperature is more than 4 °C in max. frequency operation under
2. In case of hot water supply, condense temperature is less than 58 °C in max. frequency operation with the outside temperature 7 °C D.B./6 °C W.B.
w1. Outdoor: 35 °C D.B./24 °C W.B.
(3) Heat exchanger internal capacity
Heat exchanger internal capacity must be within the capacity range shown below. If the heat exchanger below the minimum capacity is connected, it may result
in the back fl ow of liquid or the failure of the compressor.
If the heat exchanger above the maximum capacity is connected, it may result in the defi ciency in performance due to lack of refrigerant or overheating of the
compressor.
Model capacity
Maximum capacity [cm³]
Minimum capacity [cm³]
(4) Contamination maintenance
1. Wash the inside of heat exchanger to keep it clean. Be sure to RINSE not to leave fl ux. Do not use chlorine detergent when washing.
2. Be sure that the amount of contamination per unit cubic content of heat transfer pipe is less than the following amount.
Example) In case of [9.52 mm
Residual water: 0.6 mg/m, Residual oil: 0.5 mg/m, Solid foreign object: 1.8 mg/m
Thermistor position
Refer to 3.2. (FTC), 3.4. (FTC2), or 3.3. (FTC3).
Note
· Install the hydraulic fi lter at the water inlet pipework.
· Water quality should be to European Directive 98/83 EC standards
pH value of 6.5 - 8
Calcium ≤ 100 mg/L
Chrorine ≤ 100 mg/L
Iron/Manganese ≤ 0.5 mg/L
· Refrigerant pipe diameter from outdoor unit to refrigerant-water HEX (Only for SPLIT type)
Use the pipe with same diameter size as the refrigerant pipe connection diameter of outdoor unit. (Refer to outdoor unit installation manual.)
· Ensure that there is suffi cient anti-freeze chemical in the water circuit. It is recommended to use 7 : 4 anti-freeze to water ratio.
To input the abnormal signal of water pump or the abnormal lowering of water fl ow amount with non-voltage contact signal makes the outdoor unit stop forcibly.
For details, refer to 3.4.1. (FTC), 3.3.1. (FTC2), or 3.4.1. (FTC3).
· The water velocity in pipes should be kept within certain limits of material to avoid erosion, corrosion and excessive noise generation.
Be aware, and take care of , that local velocities in small pipes, bends and similar obstructions can exceed the values above.
e.g.) Copper: 1.5 m/s
Warning:
· Always use water that meets the above quality requirements. Using water that does not meet these standards may result in damage to the system
pipework and heating components.
· Never use anything other than water as a medium. It may cause a fi re or an explosion.
· Do not use heated or cooled water that is produced by the air to water heat pump directly for drinking or cooking, or swimming pool. There is a risk
to damage your health. There is also a risk that installing the water heat exchanger may corrode if the necessary water quality for air to water heat
pump system cannot be maintained. If you wish to use the heated or cooled water from the heated pump for these purposes, take measure such as
to the second heat exchanger within the water piping system.
C-56
C-56
35
50
60
1800
1800
1800
420
420
600
w1
the cooling rated conditions.
71
100
125
2130
3000
3750
710
1000
1250
140
200
250
4200
6000
7500
1400
2000
2500