Ambient Conditions - Siemens SINAMICS G120 Hardware Installation Manual

Pm230 power modules, ip55
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

7.4

Ambient conditions

Property
Ambient conditions for transport in the transport packaging
Climatic ambient conditions
Mechanical ambient condi-
tions
Protection against chemical
substances
Biological environmental
conditions
Ambient conditions for long-term storage in the product packaging
Climatic ambient conditions
Mechanical ambient condi-
tions
Protection against chemical
substances
Biological environmental
conditions
Ambient conditions in operation
Installation altitude
Climatic ambient conditions
1)
Mechanical ambient condi-
tions
Protection against chemical
substances
Biological environmental
conditions
Pollution
Cooling
Cooling air
Increased ruggedness regarding temperature range and relative humidity; therefore better than Class 3K3 to EN 60721-
1)
3-3
Observe the permissible ambient temperatures for the Control Unit and possibly the operator panel (IOP or BOP-2).
2)
PM230 Power Module, IP55
Hardware Installation Manual, 12/2016, A5E35319202B AB
Version
- 25 °C ... + 55 °C, Class 1K3 according to EN 60721-3-1
Shock and vibration permissible, Class 2M3 according to EN 60721-3-2
Protected according to Class 2C2 to EN 60721-3-2
Suitable according to Class 2B1 to EN 60721-3-2
- 40 °C ... + 70 °C, Class 2K4 according to EN 60721-3-2
Maximum humidity 95% at 40 °C
Shock and vibration permissible, Class 1M2 according to EN 60721-3-1
Protected according to Class 1C2 to EN 60721-3-1
Suitable according to Class 1B1 according to EN 60721-3-1
Up to 1,000 m above sea level without derating,
> 1,000 m
Restrictions for special ambient conditions (Page 57)
Temperature range without derating
LO base load power:
HO base load power:
For higher temperatures.
Restrictions for special ambient conditions (Page 57)
Relative humidity: 5 ... 95%, condensation not permitted
Oil mist, salt mist, ice formation, condensation, dripping water, spraying water, splashing
water and water jets are not permitted
Shock and vibration permissible, Class 3M2 according to EN 60721-3-3
Protected acc. to Class 3C2 to EN 60721-3-3
Suitable for Class 3B1 according to EN 60721-3-3
Suitable for environments with degree of pollution 2 according to EN 61800-5-1
Protected from contact with dangerous parts, dust, spray water and water jets
Forced air cooling AF, according to EN 60146
Clean and dry air
2)
-10 °C ... 40 °C
-10 °C ... 50 °C
Technical data
7.4 Ambient conditions
51