APPENDIX A - HANDHELD INTERROGATOR
A.5.1 Main Menu
This menu consists of the following sub menu options:
Display
Calibrate
Diagnose
Config
Chg Mode
Power Off
A.5.2 Display Menu
This sub menu displays gas and other unit readings. It has the following options:
Gas Reading
Signal magnitude
Dynamic Reserve
S/W Version
Gas Reading
Display the gas type and system status. The display is in the following format:
where:
gggggggg
rrrrrr
uuuu
/
Display gas and other unit readings.
Install and calibrate the system, force the analogue output,
show the calibration coefficients or show the instrument status.
Inspect the fault and warning logs, perform a self-test or
perform a soft reset.
Read the configuration parameters of the unit, update the user
configuration parameters.
Toggle the operating mode of the interrogator.
Switch the interrogator off.
Display the gas type and system status.
Show the level of the sample and reference signals.
Shows the acceptable drop in signal level before beam block
occurs as a percentage of the current signal level.
Displays the system software version and the current time and
date.
Excel gggggggg
rrrrrr uuuu /
Gas name. For a special gas table this shows <Gnnn> where nnn
is the identifier.
Gas reading.
Measurement units.
This is a status character which indicates one of the following:
/
-
A spinning line shows the system is operating normally
i.e. in a fully active state.
-
A stationery line shows the system is in an inactive
|
state.
-
Active Warning.
W
-
Active Fault.
F
-
Beam Block.
B
-
Alarm
A