Siemens SIPROTEC 7VE61 Manual page 27

Multifunction paralleling devices, communication module, modbus, bus mapping
Hide thumbs Also See for SIPROTEC 7VE61:

Advertisement


5HJLVWHUV  WR  (YHQW UHFRUGHU 6HTXHQFH RI (YHQWV
5HJLVWHU
40601
No. of Event recorder entries
40602
"SOE_Control"
40603
40604
40605
Message block #1
40606
40607
-
40610
40611
40612
40613
Message block #2
40614
40615
-
40618
40619
40620
40621
Message block #3
40622
40623
-
40626
SIPROTEC Modbus - Bus mapping 7VE61, 7VE63
C53000-L1840-C017-03
• Registers are write-protected (with the exception of "SOE_Control").
• Information regarding the individual information in the handshake register, the data
type "Message block" and the evaluation of Event recorder entries you find in the
manual "SIPROTEC Communication module, Modbus - Communication profile"
(ref. to page i).
• Only the annunciation "Data invalid" (ref. to chap. 1.5.3) is routed per default to the
Event recorder.
Further annunciations can be added to the Event recorder using DIGSI (ref. to chap.
"Customization of the allocations" in the manual "SIPROTEC Communication
module, Modbus - Communication profile").
'HVLJQDWLRQ
1.
A write access is rejected with exception code 03 (ILLEGAL_DATA_VALUE).
Number of Event recorder entries which still were not read
Handshake register (read/write access)
Register type / Bit offset #1
Register address #1
Message cause / Indication type #1
Value #1
Time stamp #1
Register type / Bit offset #2
Register address #2
Message cause / Indication type #2
Value #2
Time stamp #2
Register type / Bit offset #3
Register address #3
Message cause / Indication type #3
Value #3
Time stamp #3
0RGEXV UHJLVWHU PDS
1
&RPPHQWV
1-17