Siemens SIPROTEC 7VE61 Manual page 21

Multifunction paralleling devices, communication module, modbus, bus mapping
Hide thumbs Also See for SIPROTEC 7VE61:

Advertisement


,QSXW UHJLVWHUV ; UHIHUHQFHV
'HVLJQDWLRQ RI WKH
5HJLVWHU
6,3527(& REMHFWV
30001
V1 =
30002
V2 =
30003
f1 =
30004
f2 =
30005
dU =
30006
df =
30007
dα =
30008
<user-defined>
30009
<user-defined>
30010
<user-defined>
30011
<user-defined>
30012
<user-defined>
30013
<user-defined>
SIPROTEC Modbus - Bus mapping 7VE61, 7VE63
C53000-L1840-C017-03
The Input register block allows the Modbus master to read the values of the the analog
inputs of the SIPROTEC device (recorded measured values).
1RWH
• Depending on the device composition not all of the indicated analog inputs (and
corresponding Modbus registers) may be available in the SIPROTEC device.
• The pre-allocated measured values are transferred as secondary values per
default.
• Changes of the scaling of the measured values are possible in adaption to the con-
crete installation environment.
You find information about this in the manual "SIPROTEC Communication module,
Modbus - Communication profile" (ref. to page i).
&RPPHQWV
Measured value V1
Measured value V2
Measured value f1
Measured value f2
Measured value dU
Measured value df
Measured value dα
not pre-allocated
not pre-allocated
not pre-allocated
not pre-allocated
not pre-allocated
not pre-allocated
0RGEXV UHJLVWHU PDS
6FDOLQJ
 FRUUHVSRQGV WR 
3276,7 V
3276,7 V
327,67 Hz
327,67 Hz
3276,7 V
327,67 Hz
3276,7 °
-
-
-
-
-
-
,QWHUQDO
REMHFW QR
25044
25045
25046
25047
25048
25049
25050
-
-
-
-
-
-
1-11