Multifunction paralleling devices, communication module, modbus, bus mapping
Hide thumbs Also See for SIPROTEC 7VE61:

Advertisement

0RGEXV UHJLVWHU PDS

+ROGLQJ UHJLVWHUV ; UHIHUHQFHV

5HJLVWHUV  WR  6\VWHP LQIRUPDWLRQ
'HVLJQDWLRQ RI WKH
5HJLVWHU
6,3527(& REMHFWV
40001
Hardware designation of the communication
-
module (string, max. 16 characters)
40008
40009
-
Communication module software revision
40010
40011
MLFB (order number) of the SIPROTEC
-
device (string, max. 32 characters)
40026
40027
Date and time of mapping data generation
-
(string, max. 16 characters)
40034
40035
Number of selected standard mapping,
-
Revision of mapping data
40036
1-12
The Holding register block allows the Modbus master:
• query of system and diagnostic information, statistic values as well as min/max
values,
• time synchronization of the SIPROTEC device and
• reading the Event recorder (Sequence of Events).
• Registers are write-protected.
1.
A write access is rejected with exception code 03 (ILLEGAL_DATA_VALUE).
1
&RPPHQWV
"AME-GEN" for AME module,
"AMO-GEN" for AMO module
Example:
Register 40009 = 0001H, register 40010 = 0205H
Revision 1.2.5
Example:
"7VE61105EB910DB1----0D----------"
Example:
"170203095747330" corresponds to
Date: Feb. 17th, 2003
Time: 09 hours, 57 min., 47 sec. and 330 milliseconds
MSB of register 40035:
Number of selected standard mapping
LSB of register 40035 and value of register 40036:
Revision of mapping data
Example:
Register 40035 = 3102H, register 40036 = 0304H
Standard mapping 3-1, Revision 2.3.4
SIPROTEC Modbus - Bus mapping 7VE61, 7VE63