Product Overview - Honeywell GENT S-Quad Data And Installation

Sensor, sounder, speech & strobe
Table of Contents

Advertisement

Description and Commissioning information
S-Quad
Sensor, Sounder, Speech & Strobe
S-Quad
Gasket
(optional)
Base
PCB cover
Optical chamber
and sounder horn
assembly
Insect mesh
assembly
Outer housing
Strobe (Flasher)
assembly
Light-pipe / Cap
Dust cover
for head
4188-779 issue 10_12/13_S-Quad _Part 2
Base label
(optional)
PCB
Baffle ring
Black - Sensor only
White - with Speech
and/or Sounder
Lightpipes
Black ring - Heat only
Gold ring - CO
Base
The base has terminals for external cables to allow it to be
electrically connected to the panel loop circuit and to the
monitored input or output circuit. Any S-Quad device can be
plugged into a S-Quad base.
Base Gasket
The optional foam rubber base gasket (Part No: 805573) can
be fitted to the base to prevent water damage from dripping
water from the ceiling.
Base labels
An optional label (Part No: 805576) can be fitted to the base.
The label can be marked up with device location information.
Indicators
The S-Quad has a red LED that gives an indication in the event
of a fire. The LED can be configured to flash periodically, as an
'in operation' confirmation, this indication is given system-wide
at all S-Quads. The S-Quad with a CO sensor also has a blue
LED to indicate when a fire signal senses the presence of CO.
Dust Cover
A dust cover is supplied with the S-Quad, to prevent dust from
building work contaminating the sensor. The cover is removed
prior to the commissioning of the fire alarm system.