S-Quad - Message Action List
This list shows the messages that are likely to be displayed at the control panel or at a loop repeat panel in the fire system.

Message Action list

The messages displayed at the control panel or loop repeat panels are given for guidance only:
¨
fault message
¨
likely meaning of the message
¨
along with suggestions on what initial actions may be taken to rectify the problem.
"
Only the messages that are applicable will appear on the display of the control panel or loop repeat panels.
¨
The term Outstation and device are used interchangeably.
CO sensor faulty
CO sensor near end of
life
CO sensor restored
Flash memory checksum
error
Invalid Configuration
Invalid configuration
Memory corrupt
Program memory
corrupted
Sounder circuit has
failed
Sounder circuit
Restored
Speech circuit has
failed
Speech circuit
Restored
Strobe circuit has
failed
Strobe circuit
Restored
12
associated
Message
with..
Device
Device
Device
Device
Device
Loop
Processor
Card
Device
Card
Device
Device
Device
Device
Device
Device
meaning..
There is a fault with the
CO sensor.
The CO cell is nearing the
end of manufacturer
recommended life
expectancy.
The CO sensor fault has
been restored
Speech Memory
Checksum Error
EEPROM incorrectly
programmed
Loop recovered with
freeblocks ON
EEPROM checksum
failure
Checksum failure on
EPROM at midnight
There is a fault with the
sounder hardware on the
S-Quad or S-Cube.
The fault on the sounder
S-Quad or S-Cube has
been restored.
There is a hardware fault
possibly associated with
the voice chip on the
speech S-Quad or S-Cube.
The fault on the speech
S-Quad and S-Cube has
been restored.
The strobe circuit on the
S-Quad or S-Cube device
has failed
The hardware fault
associated with the strobe
has been restored.
..possible action
Replace device
Replace the device
-
Replace the device
Replace the device
This is not allowed. Switch
OFF the freeblocks and
reallocate
Replace device
Clear and ignore single
occurrence. Record in log
book
Replace the device
-
Replace the device
-
Replace the device
-