E1 Remote Control Communication Circuit Error - Mitsubishi Heavy Industries FDT40ZSXW1VH Service Manual

Hyper inverter packaged air-conditioners, split system, air to air heat pump type, ceiling cassette- 4 way type
Table of Contents

Advertisement

Error code
Remote control:
E1
1. Applicable model
All models
2. Error detection method
When normal communication
between the remote control and
the indoor unit is interrupted
for more than 2 minutes.
(Detectable only with the
remote control)
3. Condition of error displayed
Same as above
4. Presumable cause
• Defective communication
circuit between remote
control-indoor unit
• Noise
• Defective remote control
• Faulty indoor unit control PCB
Note:
If the indoor unit cannot communicate normally with the remote control for 180 seconds, the indoor unit PCB starts to reset
automatically.
LED
Green
Red
Keeps flashing Stays OFF
Indoor
5. Troubleshooting
Diagnosis
Is it possible to
reset normally by the
power reset?
NO
Turn SW7-1 to OFF. ¨ ON
Remove the wire z connecting
between indoor/outdoor units.
Power source reset
Does the drain
pump restart automatically
1 minute later?
NO
Connect the wire z connecting
between indoor/outdoor units.
61
-
Content
Remote control
communication circuit error
YES
YES
-
'19 • PAC-SM-302
Countermeasure
Malfunction by noise
Check peripheral
environment.
Defective indoor unit control
PCB ➞ Replace.
Move to E5.
(Communication error
during operation) check.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fdt50zsxw1vhFdt60zsxw1vh

Table of Contents